325 Amp Cable Size at 25 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.43V (1.81%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.43V (5.98%)
Voltage at Load23.6 VLine Loss: 141.2 W
Max Power & Breaker7.8 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A231.83 V (965.97%)0.0 V382.42 V (1593.4%)75345.8 WDrop High
2.5 mm²24 A18 A139.1 V (579.58%)0.0 V229.45 V (956.04%)45207.5 WDrop High
4 mm²32 A25 A86.94 V (362.24%)0.0 V143.41 V (597.53%)28254.7 WDrop High
6 mm²41 A32 A57.96 V (241.49%)0.0 V95.6 V (398.35%)18836.5 WDrop High
10 mm²57 A44 A34.77 V (144.9%)0.0 V57.36 V (239.01%)11301.9 WDrop High
16 mm²76 A59 A21.73 V (90.56%)2.3 V35.85 V (149.38%)7063.7 WDrop High
25 mm²101 A78 A13.91 V (57.96%)10.1 V22.95 V (95.6%)4520.7 WDrop High
35 mm²125 A97 A9.94 V (41.4%)14.1 V16.39 V (68.29%)3229.1 WDrop High
50 mm²151 A118 A6.95 V (28.98%)17.0 V11.47 V (47.8%)2260.4 WDrop High
70 mm²192 A150 A4.97 V (20.7%)19.0 V8.19 V (34.14%)1614.6 WDrop High
95 mm²232 A181 A3.66 V (15.25%)20.3 V6.04 V (25.16%)1189.7 WDrop High
120 mm²269 A210 A2.9 V (12.07%)21.1 V4.78 V (19.92%)941.8 WDrop High
150 mm²309 A241 A2.32 V (9.66%)21.7 V3.82 V (15.93%)753.5 WDrop High
185 mm²353 A275 A1.88 V (7.83%)22.1 V3.1 V (12.92%)610.9 WDrop High
240 mm²415 A324 A1.45 V (6.04%)22.6 V2.39 V (9.96%)470.9 WDrop High
300 mm²477 A372 A1.16 V (4.83%)22.8 V1.91 V (7.97%)376.7 W~ ≤5%
400 mm²570 A445 A0.87 V (3.62%)23.1 V1.43 V (5.98%)282.5 W~ ≤5%

FAQ — 325 Amp Cable Size at 25 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 325A at 25 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 325A over 25m at 24V (voltage drop: 0.43V or 1.81%).

What is the power capacity of 325A at 24V?

At unity power factor, 325A at 24V supports 7.8 kW with a standard 350A circuit breaker.