325 Amp Cable Size at 10 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 10 m (32.8 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 0.58V (2.41%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.57V (2.39%)
Voltage at Load23.4 VLine Loss: 188.4 W
Max Power & Breaker7.8 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A92.73 V (386.39%)0.0 V152.97 V (637.36%)30138.3 WDrop High
2.5 mm²24 A18 A55.64 V (231.83%)0.0 V91.78 V (382.42%)18083.0 WDrop High
4 mm²32 A25 A34.77 V (144.9%)0.0 V57.36 V (239.01%)11301.9 WDrop High
6 mm²41 A32 A23.18 V (96.6%)0.8 V38.24 V (159.34%)7534.6 WDrop High
10 mm²57 A44 A13.91 V (57.96%)10.1 V22.95 V (95.6%)4520.8 WDrop High
16 mm²76 A59 A8.69 V (36.22%)15.3 V14.34 V (59.75%)2825.5 WDrop High
25 mm²101 A78 A5.56 V (23.18%)18.4 V9.18 V (38.24%)1808.3 WDrop High
35 mm²125 A97 A3.97 V (16.56%)20.0 V6.56 V (27.32%)1291.6 WDrop High
50 mm²151 A118 A2.78 V (11.59%)21.2 V4.59 V (19.12%)904.1 WDrop High
70 mm²192 A150 A1.99 V (8.28%)22.0 V3.28 V (13.66%)645.8 WDrop High
95 mm²232 A181 A1.46 V (6.1%)22.5 V2.42 V (10.06%)475.9 WDrop High
120 mm²269 A210 A1.16 V (4.83%)22.8 V1.91 V (7.97%)376.7 WDrop High
150 mm²309 A241 A0.93 V (3.86%)23.1 V1.53 V (6.37%)301.4 WDrop High
185 mm²353 A275 A0.75 V (3.13%)23.2 V1.24 V (5.17%)244.4 W~ ≤5%
240 mm²415 A324 A0.58 V (2.41%)23.4 V0.96 V (3.98%)188.4 W✓ OK (≤3%)
300 mm²477 A372 A0.46 V (1.93%)23.5 V0.76 V (3.19%)150.7 W✓ OK (≤3%)
400 mm²570 A445 A0.35 V (1.45%)23.7 V0.57 V (2.39%)113.0 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 10 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 325A at 10 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 325A over 10m at 24V (voltage drop: 0.58V or 2.41%).

What is the power capacity of 325A at 24V?

At unity power factor, 325A at 24V supports 7.8 kW with a standard 350A circuit breaker.