⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

325 Amp Cable Size at 500 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 500 m (1640.4 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 7.53V (1.81%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 24.84V (5.99%)
Voltage at Load407.5 VLine Loss: 4238.2 W
Max Power & Breaker233.61 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4015.47 V (967.58%)0.0 V6623.65 V (1596.06%)2260375.0 WDrop High
2.5 mm²24 A18 A2409.28 V (580.55%)0.0 V3974.19 V (957.64%)1356225.0 WDrop High
4 mm²32 A25 A1505.8 V (362.84%)0.0 V2483.87 V (598.52%)847640.6 WDrop High
6 mm²41 A32 A1003.87 V (241.9%)0.0 V1655.91 V (399.02%)565093.8 WDrop High
10 mm²57 A44 A602.32 V (145.14%)0.0 V993.55 V (239.41%)339056.2 WDrop High
16 mm²76 A59 A376.45 V (90.71%)38.5 V620.97 V (149.63%)211910.2 WDrop High
25 mm²101 A78 A240.93 V (58.06%)174.1 V397.42 V (95.76%)135622.5 WDrop High
35 mm²125 A97 A172.09 V (41.47%)242.9 V283.87 V (68.4%)96873.2 WDrop High
50 mm²151 A118 A120.46 V (29.03%)294.5 V198.71 V (47.88%)67811.2 WDrop High
70 mm²192 A150 A86.05 V (20.73%)329.0 V141.94 V (34.2%)48436.6 WDrop High
95 mm²232 A181 A63.4 V (15.28%)351.6 V104.58 V (25.2%)35690.1 WDrop High
120 mm²269 A210 A50.19 V (12.09%)364.8 V82.8 V (19.95%)28254.7 WDrop High
150 mm²309 A241 A40.15 V (9.68%)374.8 V66.24 V (15.96%)22603.8 WDrop High
185 mm²353 A275 A32.56 V (7.85%)382.4 V53.71 V (12.94%)18327.4 WDrop High
240 mm²415 A324 A25.1 V (6.05%)389.9 V41.4 V (9.98%)14127.3 WDrop High
300 mm²477 A372 A20.08 V (4.84%)394.9 V33.12 V (7.98%)11301.9 W~ ≤5%
400 mm²570 A445 A15.06 V (3.63%)399.9 V24.84 V (5.99%)8476.4 W~ ≤5%

FAQ — 325 Amp Cable Size at 500 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 325A at 500 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 325A over 500m at 415V (voltage drop: 7.53V or 1.81%).

What is the power capacity of 325A at 415V?

At unity power factor, 325A at 415V supports 233.61 kW with a standard 350A circuit breaker.