⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

400 Amp Cable Size at 400 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 400 A over 400 m (1312.3 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 19.77V (2.86%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 24.46V (3.54%)
Voltage at Load670.2 VLine Loss: 13696.0 W
Max Power & Breaker478.05 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 400A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3953.69 V (573.0%)0.0 V6521.75 V (945.18%)2739200.0 WDrop High
2.5 mm²24 A18 A2372.22 V (343.8%)0.0 V3913.05 V (567.11%)1643520.0 WDrop High
4 mm²32 A25 A1482.64 V (214.87%)0.0 V2445.66 V (354.44%)1027200.0 WDrop High
6 mm²41 A32 A988.42 V (143.25%)0.0 V1630.44 V (236.3%)684800.0 WDrop High
10 mm²57 A44 A593.05 V (85.95%)96.9 V978.26 V (141.78%)410880.0 WDrop High
16 mm²76 A59 A370.66 V (53.72%)319.3 V611.41 V (88.61%)256800.0 WDrop High
25 mm²101 A78 A237.22 V (34.38%)452.8 V391.3 V (56.71%)164352.0 WDrop High
35 mm²125 A97 A169.44 V (24.56%)520.6 V279.5 V (40.51%)117394.3 WDrop High
50 mm²151 A118 A118.61 V (17.19%)571.4 V195.65 V (28.36%)82176.0 WDrop High
70 mm²192 A150 A84.72 V (12.28%)605.3 V139.75 V (20.25%)58697.1 WDrop High
95 mm²232 A181 A62.43 V (9.05%)627.6 V102.97 V (14.92%)43250.5 WDrop High
120 mm²269 A210 A49.42 V (7.16%)640.6 V81.52 V (11.81%)34240.0 WDrop High
150 mm²309 A241 A39.54 V (5.73%)650.5 V65.22 V (9.45%)27392.0 WDrop High
185 mm²353 A275 A32.06 V (4.65%)657.9 V52.88 V (7.66%)22209.7 WDrop High
240 mm²415 A324 A24.71 V (3.58%)665.3 V40.76 V (5.91%)17120.0 W~ ≤5%
300 mm²477 A372 A19.77 V (2.86%)670.2 V32.61 V (4.73%)13696.0 W✓ OK (≤3%)
400 mm²570 A445 A14.83 V (2.15%)675.2 V24.46 V (3.54%)10272.0 W✓ OK (≤3%)

FAQ — 400 Amp Cable Size at 400 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 400A at 400 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 400A over 400m at 690V (voltage drop: 19.77V or 2.86%).

What is the power capacity of 400A at 690V?

At unity power factor, 400A at 690V supports 478.05 kW with a standard 400A circuit breaker.