425 Amp Cable Size at 100 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 5.25V (1.27%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.5V (1.57%)
Voltage at Load409.7 VLine Loss: 3865.4 W
Max Power & Breaker305.49 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1050.2 V (253.06%)0.0 V1732.34 V (417.43%)773075.0 WDrop High
2.5 mm²24 A18 A630.12 V (151.84%)0.0 V1039.4 V (250.46%)463845.0 WDrop High
4 mm²32 A25 A393.83 V (94.9%)21.2 V649.63 V (156.54%)289903.1 WDrop High
6 mm²41 A32 A262.55 V (63.27%)152.4 V433.08 V (104.36%)193268.7 WDrop High
10 mm²57 A44 A157.53 V (37.96%)257.5 V259.85 V (62.61%)115961.2 WDrop High
16 mm²76 A59 A98.46 V (23.72%)316.5 V162.41 V (39.13%)72475.8 WDrop High
25 mm²101 A78 A63.01 V (15.18%)352.0 V103.94 V (25.05%)46384.5 WDrop High
35 mm²125 A97 A45.01 V (10.85%)370.0 V74.24 V (17.89%)33131.8 WDrop High
50 mm²151 A118 A31.51 V (7.59%)383.5 V51.97 V (12.52%)23192.2 WDrop High
70 mm²192 A150 A22.5 V (5.42%)392.5 V37.12 V (8.94%)16565.9 WDrop High
95 mm²232 A181 A16.58 V (4.0%)398.4 V27.35 V (6.59%)12206.4 WDrop High
120 mm²269 A210 A13.13 V (3.16%)401.9 V21.65 V (5.22%)9663.4 WDrop High
150 mm²309 A241 A10.5 V (2.53%)404.5 V17.32 V (4.17%)7730.7 WDrop High
185 mm²353 A275 A8.52 V (2.05%)406.5 V14.05 V (3.38%)6268.2 WDrop High
240 mm²415 A324 A6.56 V (1.58%)408.4 V10.83 V (2.61%)4831.7 WDrop High
300 mm²477 A372 A5.25 V (1.27%)409.7 V8.66 V (2.09%)3865.4 W✓ OK (≤3%)
400 mm²570 A445 A3.94 V (0.95%)411.1 V6.5 V (1.57%)2899.0 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 100 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 425A at 100 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 425A over 100m at 415V (voltage drop: 5.25V or 1.27%).

What is the power capacity of 425A at 415V?

At unity power factor, 425A at 415V supports 305.49 kW with a standard 450A circuit breaker.