425 Amp Cable Size at 300 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 300 m (984.3 ft).

Copper Cable (≤3% Drop)10× 400 mm²Drop: 1.36V (2.84%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 22.5V (46.88%)
Voltage at Load46.6 VLine Loss: 579.8 W
Max Power & Breaker20.4 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3638.0 V (7579.17%)0.0 V6001.0 V (12502.08%)1546150.0 WDrop High
2.5 mm²24 A18 A2182.8 V (4547.5%)0.0 V3600.6 V (7501.25%)927690.0 WDrop High
4 mm²32 A25 A1364.25 V (2842.19%)0.0 V2250.38 V (4688.28%)579806.2 WDrop High
6 mm²41 A32 A909.5 V (1894.79%)0.0 V1500.25 V (3125.52%)386537.5 WDrop High
10 mm²57 A44 A545.7 V (1136.88%)0.0 V900.15 V (1875.31%)231922.5 WDrop High
16 mm²76 A59 A341.06 V (710.55%)0.0 V562.59 V (1172.07%)144951.6 WDrop High
25 mm²101 A78 A218.28 V (454.75%)0.0 V360.06 V (750.12%)92769.0 WDrop High
35 mm²125 A97 A155.91 V (324.82%)0.0 V257.19 V (535.8%)66263.6 WDrop High
50 mm²151 A118 A109.14 V (227.37%)0.0 V180.03 V (375.06%)46384.5 WDrop High
70 mm²192 A150 A77.96 V (162.41%)0.0 V128.59 V (267.9%)33131.8 WDrop High
95 mm²232 A181 A57.44 V (119.67%)0.0 V94.75 V (197.4%)24412.9 WDrop High
120 mm²269 A210 A45.48 V (94.74%)2.5 V75.01 V (156.28%)19326.9 WDrop High
150 mm²309 A241 A36.38 V (75.79%)11.6 V60.01 V (125.02%)15461.5 WDrop High
185 mm²353 A275 A29.5 V (61.45%)18.5 V48.66 V (101.37%)12536.4 WDrop High
240 mm²415 A324 A22.74 V (47.37%)25.3 V37.51 V (78.14%)9663.4 WDrop High
300 mm²477 A372 A18.19 V (37.9%)29.8 V30.0 V (62.51%)7730.8 WDrop High
400 mm²570 A445 A13.64 V (28.42%)34.4 V22.5 V (46.88%)5798.1 WDrop High

FAQ — 425 Amp Cable Size at 300 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 425A at 300 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10× 400 mm² copper cable for 425A over 300m at 48V (voltage drop: 1.36V or 2.84%).

What is the power capacity of 425A at 48V?

At unity power factor, 425A at 48V supports 20.4 kW with a standard 450A circuit breaker.