⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

425 Amp Cable Size at 400 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 400 m (1312.3 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 15.75V (2.28%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 25.99V (3.77%)
Voltage at Load674.2 VLine Loss: 11596.1 W
Max Power & Breaker507.92 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4200.8 V (608.81%)0.0 V6929.36 V (1004.25%)3092300.0 WDrop High
2.5 mm²24 A18 A2520.48 V (365.29%)0.0 V4157.61 V (602.55%)1855380.0 WDrop High
4 mm²32 A25 A1575.3 V (228.3%)0.0 V2598.51 V (376.6%)1159612.5 WDrop High
6 mm²41 A32 A1050.2 V (152.2%)0.0 V1732.34 V (251.06%)773075.0 WDrop High
10 mm²57 A44 A630.12 V (91.32%)59.9 V1039.4 V (150.64%)463845.0 WDrop High
16 mm²76 A59 A393.83 V (57.08%)296.2 V649.63 V (94.15%)289903.1 WDrop High
25 mm²101 A78 A252.05 V (36.53%)438.0 V415.76 V (60.26%)185538.0 WDrop High
35 mm²125 A97 A180.03 V (26.09%)510.0 V296.97 V (43.04%)132527.1 WDrop High
50 mm²151 A118 A126.02 V (18.26%)564.0 V207.88 V (30.13%)92769.0 WDrop High
70 mm²192 A150 A90.02 V (13.05%)600.0 V148.49 V (21.52%)66263.6 WDrop High
95 mm²232 A181 A66.33 V (9.61%)623.7 V109.41 V (15.86%)48825.8 WDrop High
120 mm²269 A210 A52.51 V (7.61%)637.5 V86.62 V (12.55%)38653.7 WDrop High
150 mm²309 A241 A42.01 V (6.09%)648.0 V69.29 V (10.04%)30923.0 WDrop High
185 mm²353 A275 A34.06 V (4.94%)655.9 V56.18 V (8.14%)25072.7 WDrop High
240 mm²415 A324 A26.26 V (3.81%)663.7 V43.31 V (6.28%)19326.9 WDrop High
300 mm²477 A372 A21.0 V (3.04%)669.0 V34.65 V (5.02%)15461.5 W~ ≤5%
400 mm²570 A445 A15.75 V (2.28%)674.2 V25.99 V (3.77%)11596.1 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 400 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 425A at 400 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 425A over 400m at 690V (voltage drop: 15.75V or 2.28%).

What is the power capacity of 425A at 690V?

At unity power factor, 425A at 690V supports 507.92 kW with a standard 450A circuit breaker.