425 Amp Cable Size at 80 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 4.2V (1.01%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.2V (1.25%)
Voltage at Load410.8 VLine Loss: 3092.3 W
Max Power & Breaker305.49 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A840.16 V (202.45%)0.0 V1385.87 V (333.94%)618460.0 WDrop High
2.5 mm²24 A18 A504.1 V (121.47%)0.0 V831.52 V (200.37%)371076.0 WDrop High
4 mm²32 A25 A315.06 V (75.92%)99.9 V519.7 V (125.23%)231922.5 WDrop High
6 mm²41 A32 A210.04 V (50.61%)205.0 V346.47 V (83.49%)154615.0 WDrop High
10 mm²57 A44 A126.02 V (30.37%)289.0 V207.88 V (50.09%)92769.0 WDrop High
16 mm²76 A59 A78.77 V (18.98%)336.2 V129.93 V (31.31%)57980.6 WDrop High
25 mm²101 A78 A50.41 V (12.15%)364.6 V83.15 V (20.04%)37107.6 WDrop High
35 mm²125 A97 A36.01 V (8.68%)379.0 V59.39 V (14.31%)26505.4 WDrop High
50 mm²151 A118 A25.2 V (6.07%)389.8 V41.58 V (10.02%)18553.8 WDrop High
70 mm²192 A150 A18.0 V (4.34%)397.0 V29.7 V (7.16%)13252.7 WDrop High
95 mm²232 A181 A13.27 V (3.2%)401.7 V21.88 V (5.27%)9765.2 WDrop High
120 mm²269 A210 A10.5 V (2.53%)404.5 V17.32 V (4.17%)7730.8 WDrop High
150 mm²309 A241 A8.4 V (2.02%)406.6 V13.86 V (3.34%)6184.6 WDrop High
185 mm²353 A275 A6.81 V (1.64%)408.2 V11.24 V (2.71%)5014.5 WDrop High
240 mm²415 A324 A5.25 V (1.27%)409.7 V8.66 V (2.09%)3865.4 WDrop High
300 mm²477 A372 A4.2 V (1.01%)410.8 V6.93 V (1.67%)3092.3 W✓ OK (≤3%)
400 mm²570 A445 A3.15 V (0.76%)411.8 V5.2 V (1.25%)2319.2 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 80 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 425A at 80 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 425A over 80m at 415V (voltage drop: 4.2V or 1.01%).

What is the power capacity of 425A at 415V?

At unity power factor, 425A at 415V supports 305.49 kW with a standard 450A circuit breaker.