425 Amp Cable Size at 90 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 90 m (295.3 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 4.73V (0.68%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.85V (0.85%)
Voltage at Load685.3 VLine Loss: 3478.8 W
Max Power & Breaker507.92 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A945.18 V (136.98%)0.0 V1559.11 V (225.96%)695767.5 WDrop High
2.5 mm²24 A18 A567.11 V (82.19%)122.9 V935.46 V (135.57%)417460.5 WDrop High
4 mm²32 A25 A354.44 V (51.37%)335.6 V584.66 V (84.73%)260912.8 WDrop High
6 mm²41 A32 A236.3 V (34.25%)453.7 V389.78 V (56.49%)173941.9 WDrop High
10 mm²57 A44 A141.78 V (20.55%)548.2 V233.87 V (33.89%)104365.1 WDrop High
16 mm²76 A59 A88.61 V (12.84%)601.4 V146.17 V (21.18%)65228.2 WDrop High
25 mm²101 A78 A56.71 V (8.22%)633.3 V93.55 V (13.56%)41746.0 WDrop High
35 mm²125 A97 A40.51 V (5.87%)649.5 V66.82 V (9.68%)29818.6 WDrop High
50 mm²151 A118 A28.36 V (4.11%)661.6 V46.77 V (6.78%)20873.0 WDrop High
70 mm²192 A150 A20.25 V (2.94%)669.7 V33.41 V (4.84%)14909.3 WDrop High
95 mm²232 A181 A14.92 V (2.16%)675.1 V24.62 V (3.57%)10985.8 WDrop High
120 mm²269 A210 A11.81 V (1.71%)678.2 V19.49 V (2.82%)8697.1 WDrop High
150 mm²309 A241 A9.45 V (1.37%)680.5 V15.59 V (2.26%)6957.7 WDrop High
185 mm²353 A275 A7.66 V (1.11%)682.3 V12.64 V (1.83%)5641.4 WDrop High
240 mm²415 A324 A5.91 V (0.86%)684.1 V9.74 V (1.41%)4348.5 WDrop High
300 mm²477 A372 A4.73 V (0.68%)685.3 V7.8 V (1.13%)3478.8 W✓ OK (≤3%)
400 mm²570 A445 A3.54 V (0.51%)686.5 V5.85 V (0.85%)2609.1 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 90 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 425A at 90 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 425A over 90m at 690V (voltage drop: 4.73V or 0.68%).

What is the power capacity of 425A at 690V?

At unity power factor, 425A at 690V supports 507.92 kW with a standard 450A circuit breaker.