5 Amp Cable Size at 100 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 5 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 1.34V (2.79%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 1.41V (2.94%)
Voltage at Load46.7 VLine Loss: 6.7 W
Max Power & Breaker0.24 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A14.27 V (29.72%)33.7 V23.53 V (49.03%)71.3 WDrop High
2.5 mm²24 A18 A8.56 V (17.83%)39.4 V14.12 V (29.42%)42.8 WDrop High
4 mm²32 A25 A5.35 V (11.15%)42.6 V8.82 V (18.39%)26.7 WDrop High
6 mm²41 A32 A3.57 V (7.43%)44.4 V5.88 V (12.26%)17.8 WDrop High
10 mm²57 A44 A2.14 V (4.46%)45.9 V3.53 V (7.35%)10.7 W~ ≤5%
16 mm²76 A59 A1.34 V (2.79%)46.7 V2.21 V (4.6%)6.7 W✓ OK (≤3%)
25 mm²101 A78 A0.86 V (1.78%)47.1 V1.41 V (2.94%)4.3 W✓ OK (≤3%)
35 mm²125 A97 A0.61 V (1.27%)47.4 V1.01 V (2.1%)3.1 W✓ OK (≤3%)
50 mm²151 A118 A0.43 V (0.89%)47.6 V0.71 V (1.47%)2.1 W✓ OK (≤3%)
70 mm²192 A150 A0.31 V (0.64%)47.7 V0.5 V (1.05%)1.5 W✓ OK (≤3%)
95 mm²232 A181 A0.23 V (0.47%)47.8 V0.37 V (0.77%)1.1 W✓ OK (≤3%)
120 mm²269 A210 A0.18 V (0.37%)47.8 V0.29 V (0.61%)0.9 W✓ OK (≤3%)
150 mm²309 A241 A0.14 V (0.3%)47.9 V0.24 V (0.49%)0.7 W✓ OK (≤3%)
185 mm²353 A275 A0.12 V (0.24%)47.9 V0.19 V (0.4%)0.6 W✓ OK (≤3%)
240 mm²415 A324 A0.09 V (0.19%)47.9 V0.15 V (0.31%)0.4 W✓ OK (≤3%)
300 mm²477 A372 A0.07 V (0.15%)47.9 V0.12 V (0.25%)0.4 W✓ OK (≤3%)
400 mm²570 A445 A0.05 V (0.11%)47.9 V0.09 V (0.18%)0.3 W✓ OK (≤3%)

FAQ — 5 Amp Cable Size at 100 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 5A at 100 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 5A over 100m at 48V (voltage drop: 1.34V or 2.79%).

What is the power capacity of 5A at 48V?

At unity power factor, 5A at 48V supports 0.24 kW with a standard 6A circuit breaker.