550 Amp Cable Size at 150 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 150 m (492.1 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 7.64V (1.84%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 12.61V (3.04%)
Voltage at Load407.4 VLine Loss: 7282.7 W
Max Power & Breaker395.34 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2038.62 V (491.23%)0.0 V3362.78 V (810.31%)1942050.0 WDrop High
2.5 mm²24 A18 A1223.17 V (294.74%)0.0 V2017.67 V (486.18%)1165230.0 WDrop High
4 mm²32 A25 A764.48 V (184.21%)0.0 V1261.04 V (303.87%)728268.8 WDrop High
6 mm²41 A32 A509.66 V (122.81%)0.0 V840.69 V (202.58%)485512.5 WDrop High
10 mm²57 A44 A305.79 V (73.69%)109.2 V504.42 V (121.55%)291307.5 WDrop High
16 mm²76 A59 A191.12 V (46.05%)223.9 V315.26 V (75.97%)182067.2 WDrop High
25 mm²101 A78 A122.32 V (29.47%)292.7 V201.77 V (48.62%)116523.0 WDrop High
35 mm²125 A97 A87.37 V (21.05%)327.6 V144.12 V (34.73%)83230.7 WDrop High
50 mm²151 A118 A61.16 V (14.74%)353.8 V100.88 V (24.31%)58261.5 WDrop High
70 mm²192 A150 A43.68 V (10.53%)371.3 V72.06 V (17.36%)41615.4 WDrop High
95 mm²232 A181 A32.19 V (7.76%)382.8 V53.1 V (12.79%)30663.9 WDrop High
120 mm²269 A210 A25.48 V (6.14%)389.5 V42.03 V (10.13%)24275.6 WDrop High
150 mm²309 A241 A20.39 V (4.91%)394.6 V33.63 V (8.1%)19420.5 WDrop High
185 mm²353 A275 A16.53 V (3.98%)398.5 V27.27 V (6.57%)15746.4 WDrop High
240 mm²415 A324 A12.74 V (3.07%)402.3 V21.02 V (5.06%)12137.8 WDrop High
300 mm²477 A372 A10.19 V (2.46%)404.8 V16.81 V (4.05%)9710.2 WDrop High
400 mm²570 A445 A7.64 V (1.84%)407.4 V12.61 V (3.04%)7282.7 W✓ OK (≤3%)

FAQ — 550 Amp Cable Size at 150 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 550A at 150 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 550A over 150m at 415V (voltage drop: 7.64V or 1.84%).

What is the power capacity of 550A at 415V?

At unity power factor, 550A at 415V supports 395.34 kW with a standard 600A circuit breaker.