700 Amp Cable Size at 600 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 700 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)4× 400 mm²Drop: 9.73V (2.35%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 64.2V (15.47%)
Voltage at Load405.3 VLine Loss: 11796.8 W
Max Power & Breaker503.16 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A10378.45 V (2500.83%)0.0 V17119.59 V (4125.2%)12583200.0 WDrop High
2.5 mm²24 A18 A6227.07 V (1500.5%)0.0 V10271.75 V (2475.12%)7549920.0 WDrop High
4 mm²32 A25 A3891.92 V (937.81%)0.0 V6419.85 V (1546.95%)4718700.0 WDrop High
6 mm²41 A32 A2594.61 V (625.21%)0.0 V4279.9 V (1031.3%)3145800.0 WDrop High
10 mm²57 A44 A1556.77 V (375.12%)0.0 V2567.94 V (618.78%)1887480.0 WDrop High
16 mm²76 A59 A972.98 V (234.45%)0.0 V1604.96 V (386.74%)1179675.0 WDrop High
25 mm²101 A78 A622.71 V (150.05%)0.0 V1027.18 V (247.51%)754992.0 WDrop High
35 mm²125 A97 A444.79 V (107.18%)0.0 V733.7 V (176.79%)539280.0 WDrop High
50 mm²151 A118 A311.35 V (75.02%)103.6 V513.59 V (123.76%)377496.0 WDrop High
70 mm²192 A150 A222.4 V (53.59%)192.6 V366.85 V (88.4%)269640.0 WDrop High
95 mm²232 A181 A163.87 V (39.49%)251.1 V270.31 V (65.13%)198682.1 WDrop High
120 mm²269 A210 A129.73 V (31.26%)285.3 V213.99 V (51.57%)157290.0 WDrop High
150 mm²309 A241 A103.78 V (25.01%)311.2 V171.2 V (41.25%)125832.0 WDrop High
185 mm²353 A275 A84.15 V (20.28%)330.9 V138.81 V (33.45%)102025.9 WDrop High
240 mm²415 A324 A64.87 V (15.63%)350.1 V107.0 V (25.78%)78645.0 WDrop High
300 mm²477 A372 A51.89 V (12.5%)363.1 V85.6 V (20.63%)62916.0 WDrop High
400 mm²570 A445 A38.92 V (9.38%)376.1 V64.2 V (15.47%)47187.0 WDrop High

FAQ — 700 Amp Cable Size at 600 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 700A at 600 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4× 400 mm² copper cable for 700A over 600m at 415V (voltage drop: 9.73V or 2.35%).

What is the power capacity of 700A at 415V?

At unity power factor, 700A at 415V supports 503.16 kW with a standard 700A circuit breaker.