700 Amp Cable Size at 600 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 700 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 19.46V (2.82%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 64.2V (9.3%)
Voltage at Load670.5 VLine Loss: 23593.5 W
Max Power & Breaker836.58 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A10378.45 V (1504.12%)0.0 V17119.59 V (2481.1%)12583200.0 WDrop High
2.5 mm²24 A18 A6227.07 V (902.47%)0.0 V10271.75 V (1488.66%)7549920.0 WDrop High
4 mm²32 A25 A3891.92 V (564.05%)0.0 V6419.85 V (930.41%)4718700.0 WDrop High
6 mm²41 A32 A2594.61 V (376.03%)0.0 V4279.9 V (620.28%)3145800.0 WDrop High
10 mm²57 A44 A1556.77 V (225.62%)0.0 V2567.94 V (372.17%)1887480.0 WDrop High
16 mm²76 A59 A972.98 V (141.01%)0.0 V1604.96 V (232.6%)1179675.0 WDrop High
25 mm²101 A78 A622.71 V (90.25%)67.3 V1027.18 V (148.87%)754992.0 WDrop High
35 mm²125 A97 A444.79 V (64.46%)245.2 V733.7 V (106.33%)539280.0 WDrop High
50 mm²151 A118 A311.35 V (45.12%)378.6 V513.59 V (74.43%)377496.0 WDrop High
70 mm²192 A150 A222.4 V (32.23%)467.6 V366.85 V (53.17%)269640.0 WDrop High
95 mm²232 A181 A163.87 V (23.75%)526.1 V270.31 V (39.18%)198682.1 WDrop High
120 mm²269 A210 A129.73 V (18.8%)560.3 V213.99 V (31.01%)157290.0 WDrop High
150 mm²309 A241 A103.78 V (15.04%)586.2 V171.2 V (24.81%)125832.0 WDrop High
185 mm²353 A275 A84.15 V (12.2%)605.9 V138.81 V (20.12%)102025.9 WDrop High
240 mm²415 A324 A64.87 V (9.4%)625.1 V107.0 V (15.51%)78645.0 WDrop High
300 mm²477 A372 A51.89 V (7.52%)638.1 V85.6 V (12.41%)62916.0 WDrop High
400 mm²570 A445 A38.92 V (5.64%)651.1 V64.2 V (9.3%)47187.0 WDrop High

FAQ — 700 Amp Cable Size at 600 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 700A at 600 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 700A over 600m at 690V (voltage drop: 19.46V or 2.82%).

What is the power capacity of 700A at 690V?

At unity power factor, 700A at 690V supports 836.58 kW with a standard 700A circuit breaker.