900 Amp Cable Size at 400 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 900 A over 400 m (1312.3 ft).

Copper Cable (≤3% Drop)3× 400 mm²Drop: 11.12V (2.68%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 55.03V (13.26%)
Voltage at Load403.9 VLine Loss: 17334.0 W
Max Power & Breaker646.92 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A8895.81 V (2143.57%)0.0 V14673.93 V (3535.89%)13867200.0 WDrop High
2.5 mm²24 A18 A5337.49 V (1286.14%)0.0 V8804.36 V (2121.53%)8320320.0 WDrop High
4 mm²32 A25 A3335.93 V (803.84%)0.0 V5502.73 V (1325.96%)5200200.0 WDrop High
6 mm²41 A32 A2223.95 V (535.89%)0.0 V3668.48 V (883.97%)3466800.0 WDrop High
10 mm²57 A44 A1334.37 V (321.54%)0.0 V2201.09 V (530.38%)2080080.0 WDrop High
16 mm²76 A59 A833.98 V (200.96%)0.0 V1375.68 V (331.49%)1300050.0 WDrop High
25 mm²101 A78 A533.75 V (128.61%)0.0 V880.44 V (212.15%)832032.0 WDrop High
35 mm²125 A97 A381.25 V (91.87%)33.8 V628.88 V (151.54%)594308.6 WDrop High
50 mm²151 A118 A266.87 V (64.31%)148.1 V440.22 V (106.08%)416016.0 WDrop High
70 mm²192 A150 A190.62 V (45.93%)224.4 V314.44 V (75.77%)297154.3 WDrop High
95 mm²232 A181 A140.46 V (33.85%)274.5 V231.69 V (55.83%)218955.8 WDrop High
120 mm²269 A210 A111.2 V (26.79%)303.8 V183.42 V (44.2%)173340.0 WDrop High
150 mm²309 A241 A88.96 V (21.44%)326.0 V146.74 V (35.36%)138672.0 WDrop High
185 mm²353 A275 A72.13 V (17.38%)342.9 V118.98 V (28.67%)112436.8 WDrop High
240 mm²415 A324 A55.6 V (13.4%)359.4 V91.71 V (22.1%)86670.0 WDrop High
300 mm²477 A372 A44.48 V (10.72%)370.5 V73.37 V (17.68%)69336.0 WDrop High
400 mm²570 A445 A33.36 V (8.04%)381.6 V55.03 V (13.26%)52002.0 WDrop High

FAQ — 900 Amp Cable Size at 400 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 900A at 400 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 3× 400 mm² copper cable for 900A over 400m at 415V (voltage drop: 11.12V or 2.68%).

What is the power capacity of 900A at 415V?

At unity power factor, 900A at 415V supports 646.92 kW with a standard 1000A circuit breaker.