900 Amp Cable Size at 400 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 900 A over 400 m (1312.3 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 16.68V (2.42%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 55.03V (7.97%)
Voltage at Load673.3 VLine Loss: 26001.0 W
Max Power & Breaker1075.6 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A8895.81 V (1289.25%)0.0 V14673.93 V (2126.66%)13867200.0 WDrop High
2.5 mm²24 A18 A5337.49 V (773.55%)0.0 V8804.36 V (1275.99%)8320320.0 WDrop High
4 mm²32 A25 A3335.93 V (483.47%)0.0 V5502.73 V (797.5%)5200200.0 WDrop High
6 mm²41 A32 A2223.95 V (322.31%)0.0 V3668.48 V (531.66%)3466800.0 WDrop High
10 mm²57 A44 A1334.37 V (193.39%)0.0 V2201.09 V (319.0%)2080080.0 WDrop High
16 mm²76 A59 A833.98 V (120.87%)0.0 V1375.68 V (199.37%)1300050.0 WDrop High
25 mm²101 A78 A533.75 V (77.35%)156.3 V880.44 V (127.6%)832032.0 WDrop High
35 mm²125 A97 A381.25 V (55.25%)308.8 V628.88 V (91.14%)594308.6 WDrop High
50 mm²151 A118 A266.87 V (38.68%)423.1 V440.22 V (63.8%)416016.0 WDrop High
70 mm²192 A150 A190.62 V (27.63%)499.4 V314.44 V (45.57%)297154.3 WDrop High
95 mm²232 A181 A140.46 V (20.36%)549.5 V231.69 V (33.58%)218955.8 WDrop High
120 mm²269 A210 A111.2 V (16.12%)578.8 V183.42 V (26.58%)173340.0 WDrop High
150 mm²309 A241 A88.96 V (12.89%)601.0 V146.74 V (21.27%)138672.0 WDrop High
185 mm²353 A275 A72.13 V (10.45%)617.9 V118.98 V (17.24%)112436.8 WDrop High
240 mm²415 A324 A55.6 V (8.06%)634.4 V91.71 V (13.29%)86670.0 WDrop High
300 mm²477 A372 A44.48 V (6.45%)645.5 V73.37 V (10.63%)69336.0 WDrop High
400 mm²570 A445 A33.36 V (4.83%)656.6 V55.03 V (7.97%)52002.0 WDrop High

FAQ — 900 Amp Cable Size at 400 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 900A at 400 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 900A over 400m at 690V (voltage drop: 16.68V or 2.42%).

What is the power capacity of 900A at 690V?

At unity power factor, 900A at 690V supports 1075.6 kW with a standard 1000A circuit breaker.