Kabeltværsnit for 110 Ampere ved 175 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 110 A over 175 m ved 230V.

Copper Cable (≤3% Drop)120 mm²Drop: 6.87V (2.99%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 5.66V (2.46%)
Voltage at Load223.1 VLine Loss: 755.2 W
Max Power & Breaker25.3 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A549.27 V (238.81%)0.0 V906.03 V (393.93%)60419.3 WDrop High
2.5 mm²24 A18 A329.56 V (143.29%)0.0 V543.62 V (236.36%)36251.6 WDrop High
4 mm²32 A25 A205.97 V (89.55%)24.0 V339.76 V (147.72%)22657.2 WDrop High
6 mm²41 A32 A137.32 V (59.7%)92.7 V226.51 V (98.48%)15104.8 WDrop High
10 mm²57 A44 A82.39 V (35.82%)147.6 V135.9 V (59.09%)9062.9 WDrop High
16 mm²76 A59 A51.49 V (22.39%)178.5 V84.94 V (36.93%)5664.3 WDrop High
25 mm²101 A78 A32.96 V (14.33%)197.0 V54.36 V (23.64%)3625.2 WDrop High
35 mm²125 A97 A23.54 V (10.23%)206.5 V38.83 V (16.88%)2589.4 WDrop High
50 mm²151 A118 A16.48 V (7.16%)213.5 V27.18 V (11.82%)1812.6 WDrop High
70 mm²192 A150 A11.77 V (5.12%)218.2 V19.41 V (8.44%)1294.7 WDrop High
95 mm²232 A181 A8.67 V (3.77%)221.3 V14.31 V (6.22%)954.0 W~ ≤5%
120 mm²269 A210 A6.87 V (2.99%)223.1 V11.33 V (4.92%)755.2 W✓ OK (≤3%)
150 mm²309 A241 A5.49 V (2.39%)224.5 V9.06 V (3.94%)604.2 W✓ OK (≤3%)
185 mm²353 A275 A4.45 V (1.94%)225.5 V7.35 V (3.19%)489.9 W✓ OK (≤3%)
240 mm²415 A324 A3.43 V (1.49%)226.6 V5.66 V (2.46%)377.6 W✓ OK (≤3%)
300 mm²477 A372 A2.75 V (1.19%)227.3 V4.53 V (1.97%)302.1 W✓ OK (≤3%)
400 mm²570 A445 A2.06 V (0.9%)227.9 V3.4 V (1.48%)226.6 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 110 Ampere ved 175 Meter (230V)

Hvilket kabeltværsnit kræves til 110A ved 175 meter (230V)?

Til 110 Ampere over 175 meter ved 230V anbefales 120 mm² kobberkabel (spændingsfald 6.87V / 2.99%).

Hvor mange kW svarer 110A ved 230V til?

Det svarer til 25.3 kW med en anbefalet sikring på 110A.