Kabeltværsnit for 110 Ampere ved 175 Meter (230V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 110 A over 175 m ved 230V.
Copper Cable (≤3% Drop)120 mm²Drop: 6.87V (2.99%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 5.66V (2.46%)
Voltage at Load223.1 VLine Loss: 755.2 W
Max Power & Breaker25.3 kW110A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 175m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 549.27 V (238.81%) | 0.0 V | 906.03 V (393.93%) | 60419.3 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 329.56 V (143.29%) | 0.0 V | 543.62 V (236.36%) | 36251.6 W | Drop High |
| 4 mm² | 32 A | 25 A | 205.97 V (89.55%) | 24.0 V | 339.76 V (147.72%) | 22657.2 W | Drop High |
| 6 mm² | 41 A | 32 A | 137.32 V (59.7%) | 92.7 V | 226.51 V (98.48%) | 15104.8 W | Drop High |
| 10 mm² | 57 A | 44 A | 82.39 V (35.82%) | 147.6 V | 135.9 V (59.09%) | 9062.9 W | Drop High |
| 16 mm² | 76 A | 59 A | 51.49 V (22.39%) | 178.5 V | 84.94 V (36.93%) | 5664.3 W | Drop High |
| 25 mm² | 101 A | 78 A | 32.96 V (14.33%) | 197.0 V | 54.36 V (23.64%) | 3625.2 W | Drop High |
| 35 mm² | 125 A | 97 A | 23.54 V (10.23%) | 206.5 V | 38.83 V (16.88%) | 2589.4 W | Drop High |
| 50 mm² | 151 A | 118 A | 16.48 V (7.16%) | 213.5 V | 27.18 V (11.82%) | 1812.6 W | Drop High |
| 70 mm² | 192 A | 150 A | 11.77 V (5.12%) | 218.2 V | 19.41 V (8.44%) | 1294.7 W | Drop High |
| 95 mm² | 232 A | 181 A | 8.67 V (3.77%) | 221.3 V | 14.31 V (6.22%) | 954.0 W | ~ ≤5% |
| 120 mm² | 269 A | 210 A | 6.87 V (2.99%) | 223.1 V | 11.33 V (4.92%) | 755.2 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 5.49 V (2.39%) | 224.5 V | 9.06 V (3.94%) | 604.2 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 4.45 V (1.94%) | 225.5 V | 7.35 V (3.19%) | 489.9 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 3.43 V (1.49%) | 226.6 V | 5.66 V (2.46%) | 377.6 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 2.75 V (1.19%) | 227.3 V | 4.53 V (1.97%) | 302.1 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 2.06 V (0.9%) | 227.9 V | 3.4 V (1.48%) | 226.6 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 110 Ampere ved 175 Meter (230V)
Hvilket kabeltværsnit kræves til 110A ved 175 meter (230V)?
Til 110 Ampere over 175 meter ved 230V anbefales 120 mm² kobberkabel (spændingsfald 6.87V / 2.99%).
Hvor mange kW svarer 110A ved 230V til?
Det svarer til 25.3 kW med en anbefalet sikring på 110A.
Related Lengths & Currents (230V)
110A · 5m (230V)110A · 10m (230V)110A · 15m (230V)110A · 20m (230V)110A · 25m (230V)110A · 30m (230V)110A · 35m (230V)110A · 40m (230V)110A · 45m (230V)110A · 50m (230V)110A · 60m (230V)110A · 70m (230V)10A · 175m (230V)16A · 175m (230V)20A · 175m (230V)25A · 175m (230V)32A · 175m (230V)40A · 175m (230V)50A · 175m (230V)63A · 175m (230V)80A · 175m (230V)100A · 175m (230V)125A · 175m (230V)160A · 175m (230V)200A · 175m (230V)