⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 110 Ampere vid 120 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 110 A över 120 m vid 400V.

Copper Cable (≤3% Drop)50 mm²Drop: 9.79V (2.45%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 11.53V (2.88%)
Voltage at Load390.2 VLine Loss: 1864.4 W
Max Power & Breaker76.21 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A326.18 V (81.54%)73.8 V538.04 V (134.51%)62145.6 WDrop High
2.5 mm²24 A18 A195.71 V (48.93%)204.3 V322.83 V (80.71%)37287.4 WDrop High
4 mm²32 A25 A122.32 V (30.58%)277.7 V201.77 V (50.44%)23304.6 WDrop High
6 mm²41 A32 A81.54 V (20.39%)318.5 V134.51 V (33.63%)15536.4 WDrop High
10 mm²57 A44 A48.93 V (12.23%)351.1 V80.71 V (20.18%)9321.8 WDrop High
16 mm²76 A59 A30.58 V (7.64%)369.4 V50.44 V (12.61%)5826.2 WDrop High
25 mm²101 A78 A19.57 V (4.89%)380.4 V32.28 V (8.07%)3728.7 WDrop High
35 mm²125 A97 A13.98 V (3.49%)386.0 V23.06 V (5.76%)2663.4 W~ ≤5%
50 mm²151 A118 A9.79 V (2.45%)390.2 V16.14 V (4.04%)1864.4 W✓ OK (≤3%)
70 mm²192 A150 A6.99 V (1.75%)393.0 V11.53 V (2.88%)1331.7 W✓ OK (≤3%)
95 mm²232 A181 A5.15 V (1.29%)394.8 V8.5 V (2.12%)981.2 W✓ OK (≤3%)
120 mm²269 A210 A4.08 V (1.02%)395.9 V6.73 V (1.68%)776.8 W✓ OK (≤3%)
150 mm²309 A241 A3.26 V (0.82%)396.7 V5.38 V (1.35%)621.5 W✓ OK (≤3%)
185 mm²353 A275 A2.64 V (0.66%)397.4 V4.36 V (1.09%)503.9 W✓ OK (≤3%)
240 mm²415 A324 A2.04 V (0.51%)398.0 V3.36 V (0.84%)388.4 W✓ OK (≤3%)
300 mm²477 A372 A1.63 V (0.41%)398.4 V2.69 V (0.67%)310.7 W✓ OK (≤3%)
400 mm²570 A445 A1.22 V (0.31%)398.8 V2.02 V (0.5%)233.0 W✓ OK (≤3%)

FAQ — Kabelarea för 110 Ampere vid 120 Meter (400V)

Vilken kabelarea krävs för 110A vid 120 meter (400V)?

För 110 Ampere över 120 meter vid 400V rekommenderas 50 mm² kopparkabel för att hålla spänningsfallet under 3% (9.79V / 2.45%).

Hur stor effekt motsvarar 110A vid 400V?

Det motsvarar 76.21 kW med en rekommenderad säkring på 110A.