Kabelarea för 110 Ampere vid 175 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 110 A över 175 m vid 400V.

Copper Cable (≤3% Drop)70 mm²Drop: 10.19V (2.55%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 9.81V (2.45%)
Voltage at Load389.8 VLine Loss: 1942.0 W
Max Power & Breaker76.21 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A475.68 V (118.92%)0.0 V784.65 V (196.16%)90629.0 WDrop High
2.5 mm²24 A18 A285.41 V (71.35%)114.6 V470.79 V (117.7%)54377.4 WDrop High
4 mm²32 A25 A178.38 V (44.59%)221.6 V294.24 V (73.56%)33985.9 WDrop High
6 mm²41 A32 A118.92 V (29.73%)281.1 V196.16 V (49.04%)22657.2 WDrop High
10 mm²57 A44 A71.35 V (17.84%)328.6 V117.7 V (29.42%)13594.3 WDrop High
16 mm²76 A59 A44.59 V (11.15%)355.4 V73.56 V (18.39%)8496.5 WDrop High
25 mm²101 A78 A28.54 V (7.14%)371.5 V47.08 V (11.77%)5437.7 WDrop High
35 mm²125 A97 A20.39 V (5.1%)379.6 V33.63 V (8.41%)3884.1 WDrop High
50 mm²151 A118 A14.27 V (3.57%)385.7 V23.54 V (5.88%)2718.9 W~ ≤5%
70 mm²192 A150 A10.19 V (2.55%)389.8 V16.81 V (4.2%)1942.0 W✓ OK (≤3%)
95 mm²232 A181 A7.51 V (1.88%)392.5 V12.39 V (3.1%)1431.0 W✓ OK (≤3%)
120 mm²269 A210 A5.95 V (1.49%)394.1 V9.81 V (2.45%)1132.9 W✓ OK (≤3%)
150 mm²309 A241 A4.76 V (1.19%)395.2 V7.85 V (1.96%)906.3 W✓ OK (≤3%)
185 mm²353 A275 A3.86 V (0.96%)396.1 V6.36 V (1.59%)734.8 W✓ OK (≤3%)
240 mm²415 A324 A2.97 V (0.74%)397.0 V4.9 V (1.23%)566.4 W✓ OK (≤3%)
300 mm²477 A372 A2.38 V (0.59%)397.6 V3.92 V (0.98%)453.1 W✓ OK (≤3%)
400 mm²570 A445 A1.78 V (0.45%)398.2 V2.94 V (0.74%)339.9 W✓ OK (≤3%)

FAQ — Kabelarea för 110 Ampere vid 175 Meter (400V)

Vilken kabelarea krävs för 110A vid 175 meter (400V)?

För 110 Ampere över 175 meter vid 400V rekommenderas 70 mm² kopparkabel för att hålla spänningsfallet under 3% (10.19V / 2.55%).

Hur stor effekt motsvarar 110A vid 400V?

Det motsvarar 76.21 kW med en rekommenderad säkring på 110A.