Kabelarea för 110 Ampere vid 45 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 110 A över 45 m vid 230V.

Copper Cable (≤3% Drop)35 mm²Drop: 6.05V (2.63%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 4.99V (2.17%)
Voltage at Load223.9 VLine Loss: 665.8 W
Max Power & Breaker25.3 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A141.24 V (61.41%)88.8 V232.98 V (101.3%)15536.4 WDrop High
2.5 mm²24 A18 A84.74 V (36.85%)145.3 V139.79 V (60.78%)9321.8 WDrop High
4 mm²32 A25 A52.96 V (23.03%)177.0 V87.37 V (37.99%)5826.1 WDrop High
6 mm²41 A32 A35.31 V (15.35%)194.7 V58.24 V (25.32%)3884.1 WDrop High
10 mm²57 A44 A21.19 V (9.21%)208.8 V34.95 V (15.19%)2330.5 WDrop High
16 mm²76 A59 A13.24 V (5.76%)216.8 V21.84 V (9.5%)1456.5 WDrop High
25 mm²101 A78 A8.47 V (3.68%)221.5 V13.98 V (6.08%)932.2 WDrop High
35 mm²125 A97 A6.05 V (2.63%)223.9 V9.98 V (4.34%)665.8 W✓ OK (≤3%)
50 mm²151 A118 A4.24 V (1.84%)225.8 V6.99 V (3.04%)466.1 W✓ OK (≤3%)
70 mm²192 A150 A3.03 V (1.32%)227.0 V4.99 V (2.17%)332.9 W✓ OK (≤3%)
95 mm²232 A181 A2.23 V (0.97%)227.8 V3.68 V (1.6%)245.3 W✓ OK (≤3%)
120 mm²269 A210 A1.77 V (0.77%)228.2 V2.91 V (1.27%)194.2 W✓ OK (≤3%)
150 mm²309 A241 A1.41 V (0.61%)228.6 V2.33 V (1.01%)155.4 W✓ OK (≤3%)
185 mm²353 A275 A1.15 V (0.5%)228.9 V1.89 V (0.82%)126.0 W✓ OK (≤3%)
240 mm²415 A324 A0.88 V (0.38%)229.1 V1.46 V (0.63%)97.1 W✓ OK (≤3%)
300 mm²477 A372 A0.71 V (0.31%)229.3 V1.16 V (0.51%)77.7 W✓ OK (≤3%)
400 mm²570 A445 A0.53 V (0.23%)229.5 V0.87 V (0.38%)58.3 W✓ OK (≤3%)

FAQ — Kabelarea för 110 Ampere vid 45 Meter (230V)

Vilken kabelarea krävs för 110A vid 45 meter (230V)?

För 110 Ampere över 45 meter vid 230V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (6.05V / 2.63%).

Hur stor effekt motsvarar 110A vid 230V?

Det motsvarar 25.3 kW med en rekommenderad säkring på 110A.