Kabelarea för 110 Ampere vid 70 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 110 A över 70 m vid 230V.

Copper Cable (≤3% Drop)50 mm²Drop: 6.59V (2.87%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 5.72V (2.49%)
Voltage at Load223.4 VLine Loss: 725.0 W
Max Power & Breaker25.3 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A219.71 V (95.52%)10.3 V362.41 V (157.57%)24167.7 WDrop High
2.5 mm²24 A18 A131.82 V (57.31%)98.2 V217.45 V (94.54%)14500.6 WDrop High
4 mm²32 A25 A82.39 V (35.82%)147.6 V135.91 V (59.09%)9062.9 WDrop High
6 mm²41 A32 A54.93 V (23.88%)175.1 V90.6 V (39.39%)6041.9 WDrop High
10 mm²57 A44 A32.96 V (14.33%)197.0 V54.36 V (23.64%)3625.2 WDrop High
16 mm²76 A59 A20.6 V (8.96%)209.4 V33.98 V (14.77%)2265.7 WDrop High
25 mm²101 A78 A13.18 V (5.73%)216.8 V21.74 V (9.45%)1450.1 WDrop High
35 mm²125 A97 A9.42 V (4.09%)220.6 V15.53 V (6.75%)1035.8 W~ ≤5%
50 mm²151 A118 A6.59 V (2.87%)223.4 V10.87 V (4.73%)725.0 W✓ OK (≤3%)
70 mm²192 A150 A4.71 V (2.05%)225.3 V7.77 V (3.38%)517.9 W✓ OK (≤3%)
95 mm²232 A181 A3.47 V (1.51%)226.5 V5.72 V (2.49%)381.6 W✓ OK (≤3%)
120 mm²269 A210 A2.75 V (1.19%)227.3 V4.53 V (1.97%)302.1 W✓ OK (≤3%)
150 mm²309 A241 A2.2 V (0.96%)227.8 V3.62 V (1.58%)241.7 W✓ OK (≤3%)
185 mm²353 A275 A1.78 V (0.77%)228.2 V2.94 V (1.28%)196.0 W✓ OK (≤3%)
240 mm²415 A324 A1.37 V (0.6%)228.6 V2.27 V (0.98%)151.0 W✓ OK (≤3%)
300 mm²477 A372 A1.1 V (0.48%)228.9 V1.81 V (0.79%)120.8 W✓ OK (≤3%)
400 mm²570 A445 A0.82 V (0.36%)229.2 V1.36 V (0.59%)90.6 W✓ OK (≤3%)

FAQ — Kabelarea för 110 Ampere vid 70 Meter (230V)

Vilken kabelarea krävs för 110A vid 70 meter (230V)?

För 110 Ampere över 70 meter vid 230V rekommenderas 50 mm² kopparkabel för att hålla spänningsfallet under 3% (6.59V / 2.87%).

Hur stor effekt motsvarar 110A vid 230V?

Det motsvarar 25.3 kW med en rekommenderad säkring på 110A.