Kabelarea för 110 Ampere vid 20 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 110 A över 20 m vid 230V.
Copper Cable (≤3% Drop)35 mm²Drop: 2.69V (1.17%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 3.11V (1.35%)
Voltage at Load227.3 VLine Loss: 295.9 W
Max Power & Breaker25.3 kW110A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 20m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 62.77 V (27.29%) | 167.2 V | 103.55 V (45.02%) | 6905.1 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 37.66 V (16.38%) | 192.3 V | 62.13 V (27.01%) | 4143.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 23.54 V (10.23%) | 206.5 V | 38.83 V (16.88%) | 2589.4 W | Drop High |
| 6 mm² | 41 A | 32 A | 15.69 V (6.82%) | 214.3 V | 25.89 V (11.26%) | 1726.3 W | Drop High |
| 10 mm² | 57 A | 44 A | 9.42 V (4.09%) | 220.6 V | 15.53 V (6.75%) | 1035.8 W | Drop High |
| 16 mm² | 76 A | 59 A | 5.88 V (2.56%) | 224.1 V | 9.71 V (4.22%) | 647.4 W | Drop High |
| 25 mm² | 101 A | 78 A | 3.77 V (1.64%) | 226.2 V | 6.21 V (2.7%) | 414.3 W | Drop High |
| 35 mm² | 125 A | 97 A | 2.69 V (1.17%) | 227.3 V | 4.44 V (1.93%) | 295.9 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 1.88 V (0.82%) | 228.1 V | 3.11 V (1.35%) | 207.2 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 1.35 V (0.58%) | 228.7 V | 2.22 V (0.96%) | 148.0 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.99 V (0.43%) | 229.0 V | 1.63 V (0.71%) | 109.0 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.78 V (0.34%) | 229.2 V | 1.29 V (0.56%) | 86.3 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.63 V (0.27%) | 229.4 V | 1.04 V (0.45%) | 69.1 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.51 V (0.22%) | 229.5 V | 0.84 V (0.37%) | 56.0 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.39 V (0.17%) | 229.6 V | 0.65 V (0.28%) | 43.2 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.31 V (0.14%) | 229.7 V | 0.52 V (0.23%) | 34.5 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.24 V (0.1%) | 229.8 V | 0.39 V (0.17%) | 25.9 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 110 Ampere vid 20 Meter (230V)
Vilken kabelarea krävs för 110A vid 20 meter (230V)?
För 110 Ampere över 20 meter vid 230V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (2.69V / 1.17%).
Hur stor effekt motsvarar 110A vid 230V?
Det motsvarar 25.3 kW med en rekommenderad säkring på 110A.
Related Lengths & Currents (230V)
110A · 5m (230V)110A · 10m (230V)110A · 15m (230V)110A · 25m (230V)110A · 30m (230V)110A · 35m (230V)110A · 40m (230V)110A · 45m (230V)110A · 50m (230V)110A · 60m (230V)110A · 70m (230V)10A · 20m (230V)16A · 20m (230V)20A · 20m (230V)25A · 20m (230V)32A · 20m (230V)40A · 20m (230V)50A · 20m (230V)63A · 20m (230V)80A · 20m (230V)100A · 20m (230V)125A · 20m (230V)160A · 20m (230V)200A · 20m (230V)