Kabelarea för 110 Ampere vid 20 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 110 A över 20 m vid 230V.

Copper Cable (≤3% Drop)35 mm²Drop: 2.69V (1.17%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 3.11V (1.35%)
Voltage at Load227.3 VLine Loss: 295.9 W
Max Power & Breaker25.3 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A62.77 V (27.29%)167.2 V103.55 V (45.02%)6905.1 WDrop High
2.5 mm²24 A18 A37.66 V (16.38%)192.3 V62.13 V (27.01%)4143.0 WDrop High
4 mm²32 A25 A23.54 V (10.23%)206.5 V38.83 V (16.88%)2589.4 WDrop High
6 mm²41 A32 A15.69 V (6.82%)214.3 V25.89 V (11.26%)1726.3 WDrop High
10 mm²57 A44 A9.42 V (4.09%)220.6 V15.53 V (6.75%)1035.8 WDrop High
16 mm²76 A59 A5.88 V (2.56%)224.1 V9.71 V (4.22%)647.4 WDrop High
25 mm²101 A78 A3.77 V (1.64%)226.2 V6.21 V (2.7%)414.3 WDrop High
35 mm²125 A97 A2.69 V (1.17%)227.3 V4.44 V (1.93%)295.9 W✓ OK (≤3%)
50 mm²151 A118 A1.88 V (0.82%)228.1 V3.11 V (1.35%)207.2 W✓ OK (≤3%)
70 mm²192 A150 A1.35 V (0.58%)228.7 V2.22 V (0.96%)148.0 W✓ OK (≤3%)
95 mm²232 A181 A0.99 V (0.43%)229.0 V1.63 V (0.71%)109.0 W✓ OK (≤3%)
120 mm²269 A210 A0.78 V (0.34%)229.2 V1.29 V (0.56%)86.3 W✓ OK (≤3%)
150 mm²309 A241 A0.63 V (0.27%)229.4 V1.04 V (0.45%)69.1 W✓ OK (≤3%)
185 mm²353 A275 A0.51 V (0.22%)229.5 V0.84 V (0.37%)56.0 W✓ OK (≤3%)
240 mm²415 A324 A0.39 V (0.17%)229.6 V0.65 V (0.28%)43.2 W✓ OK (≤3%)
300 mm²477 A372 A0.31 V (0.14%)229.7 V0.52 V (0.23%)34.5 W✓ OK (≤3%)
400 mm²570 A445 A0.24 V (0.1%)229.8 V0.39 V (0.17%)25.9 W✓ OK (≤3%)

FAQ — Kabelarea för 110 Ampere vid 20 Meter (230V)

Vilken kabelarea krävs för 110A vid 20 meter (230V)?

För 110 Ampere över 20 meter vid 230V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (2.69V / 1.17%).

Hur stor effekt motsvarar 110A vid 230V?

Det motsvarar 25.3 kW med en rekommenderad säkring på 110A.