Kabelarea för 110 Ampere vid 5 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 110 A över 5 m vid 230V.
Copper Cable (≤3% Drop)35 mm²Drop: 0.67V (0.29%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 0.78V (0.34%)
Voltage at Load229.3 VLine Loss: 74.0 W
Max Power & Breaker25.3 kW110A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 5m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 15.69 V (6.82%) | 214.3 V | 25.89 V (11.26%) | 1726.3 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 9.42 V (4.09%) | 220.6 V | 15.53 V (6.75%) | 1035.8 W | Drop High |
| 4 mm² | 32 A | 25 A | 5.88 V (2.56%) | 224.1 V | 9.71 V (4.22%) | 647.4 W | Drop High |
| 6 mm² | 41 A | 32 A | 3.92 V (1.71%) | 226.1 V | 6.47 V (2.81%) | 431.6 W | Drop High |
| 10 mm² | 57 A | 44 A | 2.35 V (1.02%) | 227.6 V | 3.88 V (1.69%) | 258.9 W | Drop High |
| 16 mm² | 76 A | 59 A | 1.47 V (0.64%) | 228.5 V | 2.43 V (1.06%) | 161.8 W | Drop High |
| 25 mm² | 101 A | 78 A | 0.94 V (0.41%) | 229.1 V | 1.55 V (0.68%) | 103.6 W | Drop High |
| 35 mm² | 125 A | 97 A | 0.67 V (0.29%) | 229.3 V | 1.11 V (0.48%) | 74.0 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.47 V (0.2%) | 229.5 V | 0.78 V (0.34%) | 51.8 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.34 V (0.15%) | 229.7 V | 0.55 V (0.24%) | 37.0 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.25 V (0.11%) | 229.8 V | 0.41 V (0.18%) | 27.3 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.2 V (0.09%) | 229.8 V | 0.32 V (0.14%) | 21.6 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.16 V (0.07%) | 229.8 V | 0.26 V (0.11%) | 17.3 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.13 V (0.06%) | 229.9 V | 0.21 V (0.09%) | 14.0 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.1 V (0.04%) | 229.9 V | 0.16 V (0.07%) | 10.8 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.08 V (0.03%) | 229.9 V | 0.13 V (0.06%) | 8.6 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.06 V (0.03%) | 229.9 V | 0.1 V (0.04%) | 6.5 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 110 Ampere vid 5 Meter (230V)
Vilken kabelarea krävs för 110A vid 5 meter (230V)?
För 110 Ampere över 5 meter vid 230V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (0.67V / 0.29%).
Hur stor effekt motsvarar 110A vid 230V?
Det motsvarar 25.3 kW med en rekommenderad säkring på 110A.
Related Lengths & Currents (230V)
110A · 10m (230V)110A · 15m (230V)110A · 20m (230V)110A · 25m (230V)110A · 30m (230V)110A · 35m (230V)110A · 40m (230V)110A · 45m (230V)110A · 50m (230V)110A · 60m (230V)110A · 70m (230V)10A · 5m (230V)16A · 5m (230V)20A · 5m (230V)25A · 5m (230V)32A · 5m (230V)40A · 5m (230V)50A · 5m (230V)63A · 5m (230V)80A · 5m (230V)100A · 5m (230V)125A · 5m (230V)160A · 5m (230V)200A · 5m (230V)