⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 110 Ampere vid 35 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 110 A över 35 m vid 230V.

Copper Cable (≤3% Drop)35 mm²Drop: 4.71V (2.05%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 5.44V (2.36%)
Voltage at Load225.3 VLine Loss: 517.9 W
Max Power & Breaker25.3 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A109.85 V (47.76%)120.1 V181.21 V (78.79%)12083.9 WDrop High
2.5 mm²24 A18 A65.91 V (28.66%)164.1 V108.72 V (47.27%)7250.3 WDrop High
4 mm²32 A25 A41.2 V (17.91%)188.8 V67.95 V (29.54%)4531.4 WDrop High
6 mm²41 A32 A27.46 V (11.94%)202.5 V45.3 V (19.7%)3021.0 WDrop High
10 mm²57 A44 A16.48 V (7.16%)213.5 V27.18 V (11.82%)1812.6 WDrop High
16 mm²76 A59 A10.3 V (4.48%)219.7 V16.99 V (7.39%)1132.9 WDrop High
25 mm²101 A78 A6.59 V (2.87%)223.4 V10.87 V (4.73%)725.0 WDrop High
35 mm²125 A97 A4.71 V (2.05%)225.3 V7.77 V (3.38%)517.9 W✓ OK (≤3%)
50 mm²151 A118 A3.3 V (1.43%)226.7 V5.44 V (2.36%)362.5 W✓ OK (≤3%)
70 mm²192 A150 A2.35 V (1.02%)227.6 V3.88 V (1.69%)258.9 W✓ OK (≤3%)
95 mm²232 A181 A1.73 V (0.75%)228.3 V2.86 V (1.24%)190.8 W✓ OK (≤3%)
120 mm²269 A210 A1.37 V (0.6%)228.6 V2.27 V (0.98%)151.0 W✓ OK (≤3%)
150 mm²309 A241 A1.1 V (0.48%)228.9 V1.81 V (0.79%)120.8 W✓ OK (≤3%)
185 mm²353 A275 A0.89 V (0.39%)229.1 V1.47 V (0.64%)98.0 W✓ OK (≤3%)
240 mm²415 A324 A0.69 V (0.3%)229.3 V1.13 V (0.49%)75.5 W✓ OK (≤3%)
300 mm²477 A372 A0.55 V (0.24%)229.5 V0.91 V (0.39%)60.4 W✓ OK (≤3%)
400 mm²570 A445 A0.41 V (0.18%)229.6 V0.68 V (0.3%)45.3 W✓ OK (≤3%)

FAQ — Kabelarea för 110 Ampere vid 35 Meter (230V)

Vilken kabelarea krävs för 110A vid 35 meter (230V)?

För 110 Ampere över 35 meter vid 230V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (4.71V / 2.05%).

Hur stor effekt motsvarar 110A vid 230V?

Det motsvarar 25.3 kW med en rekommenderad säkring på 110A.