Kabelarea för 110 Ampere vid 35 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 110 A över 35 m vid 230V.
Copper Cable (≤3% Drop)35 mm²Drop: 4.71V (2.05%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 5.44V (2.36%)
Voltage at Load225.3 VLine Loss: 517.9 W
Max Power & Breaker25.3 kW110A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 35m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 109.85 V (47.76%) | 120.1 V | 181.21 V (78.79%) | 12083.9 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 65.91 V (28.66%) | 164.1 V | 108.72 V (47.27%) | 7250.3 W | Drop High |
| 4 mm² | 32 A | 25 A | 41.2 V (17.91%) | 188.8 V | 67.95 V (29.54%) | 4531.4 W | Drop High |
| 6 mm² | 41 A | 32 A | 27.46 V (11.94%) | 202.5 V | 45.3 V (19.7%) | 3021.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 16.48 V (7.16%) | 213.5 V | 27.18 V (11.82%) | 1812.6 W | Drop High |
| 16 mm² | 76 A | 59 A | 10.3 V (4.48%) | 219.7 V | 16.99 V (7.39%) | 1132.9 W | Drop High |
| 25 mm² | 101 A | 78 A | 6.59 V (2.87%) | 223.4 V | 10.87 V (4.73%) | 725.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 4.71 V (2.05%) | 225.3 V | 7.77 V (3.38%) | 517.9 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 3.3 V (1.43%) | 226.7 V | 5.44 V (2.36%) | 362.5 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 2.35 V (1.02%) | 227.6 V | 3.88 V (1.69%) | 258.9 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 1.73 V (0.75%) | 228.3 V | 2.86 V (1.24%) | 190.8 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 1.37 V (0.6%) | 228.6 V | 2.27 V (0.98%) | 151.0 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 1.1 V (0.48%) | 228.9 V | 1.81 V (0.79%) | 120.8 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.89 V (0.39%) | 229.1 V | 1.47 V (0.64%) | 98.0 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.69 V (0.3%) | 229.3 V | 1.13 V (0.49%) | 75.5 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.55 V (0.24%) | 229.5 V | 0.91 V (0.39%) | 60.4 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.41 V (0.18%) | 229.6 V | 0.68 V (0.3%) | 45.3 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 110 Ampere vid 35 Meter (230V)
Vilken kabelarea krävs för 110A vid 35 meter (230V)?
För 110 Ampere över 35 meter vid 230V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (4.71V / 2.05%).
Hur stor effekt motsvarar 110A vid 230V?
Det motsvarar 25.3 kW med en rekommenderad säkring på 110A.
Related Lengths & Currents (230V)
110A · 5m (230V)110A · 10m (230V)110A · 15m (230V)110A · 20m (230V)110A · 25m (230V)110A · 30m (230V)110A · 40m (230V)110A · 45m (230V)110A · 50m (230V)110A · 60m (230V)110A · 70m (230V)10A · 35m (230V)16A · 35m (230V)20A · 35m (230V)25A · 35m (230V)32A · 35m (230V)40A · 35m (230V)50A · 35m (230V)63A · 35m (230V)80A · 35m (230V)100A · 35m (230V)125A · 35m (230V)160A · 35m (230V)200A · 35m (230V)