Kabelarea för 110 Ampere vid 60 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 110 A över 60 m vid 230V.
Copper Cable (≤3% Drop)50 mm²Drop: 5.65V (2.46%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 6.66V (2.89%)
Voltage at Load224.4 VLine Loss: 621.5 W
Max Power & Breaker25.3 kW110A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 60m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 188.32 V (81.88%) | 41.7 V | 310.64 V (135.06%) | 20715.2 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 112.99 V (49.13%) | 117.0 V | 186.38 V (81.04%) | 12429.1 W | Drop High |
| 4 mm² | 32 A | 25 A | 70.62 V (30.7%) | 159.4 V | 116.49 V (50.65%) | 7768.2 W | Drop High |
| 6 mm² | 41 A | 32 A | 47.08 V (20.47%) | 182.9 V | 77.66 V (33.77%) | 5178.8 W | Drop High |
| 10 mm² | 57 A | 44 A | 28.25 V (12.28%) | 201.8 V | 46.6 V (20.26%) | 3107.3 W | Drop High |
| 16 mm² | 76 A | 59 A | 17.66 V (7.68%) | 212.3 V | 29.12 V (12.66%) | 1942.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 11.3 V (4.91%) | 218.7 V | 18.64 V (8.1%) | 1242.9 W | Drop High |
| 35 mm² | 125 A | 97 A | 8.07 V (3.51%) | 221.9 V | 13.31 V (5.79%) | 887.8 W | ~ ≤5% |
| 50 mm² | 151 A | 118 A | 5.65 V (2.46%) | 224.4 V | 9.32 V (4.05%) | 621.5 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 4.04 V (1.75%) | 226.0 V | 6.66 V (2.89%) | 443.9 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 2.97 V (1.29%) | 227.0 V | 4.9 V (2.13%) | 327.1 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 2.35 V (1.02%) | 227.6 V | 3.88 V (1.69%) | 258.9 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 1.88 V (0.82%) | 228.1 V | 3.11 V (1.35%) | 207.2 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 1.53 V (0.66%) | 228.5 V | 2.52 V (1.1%) | 168.0 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 1.18 V (0.51%) | 228.8 V | 1.94 V (0.84%) | 129.5 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.94 V (0.41%) | 229.1 V | 1.55 V (0.68%) | 103.6 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.71 V (0.31%) | 229.3 V | 1.16 V (0.51%) | 77.7 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 110 Ampere vid 60 Meter (230V)
Vilken kabelarea krävs för 110A vid 60 meter (230V)?
För 110 Ampere över 60 meter vid 230V rekommenderas 50 mm² kopparkabel för att hålla spänningsfallet under 3% (5.65V / 2.46%).
Hur stor effekt motsvarar 110A vid 230V?
Det motsvarar 25.3 kW med en rekommenderad säkring på 110A.
Related Lengths & Currents (230V)
110A · 5m (230V)110A · 10m (230V)110A · 15m (230V)110A · 20m (230V)110A · 25m (230V)110A · 30m (230V)110A · 35m (230V)110A · 40m (230V)110A · 45m (230V)110A · 50m (230V)110A · 70m (230V)10A · 60m (230V)16A · 60m (230V)20A · 60m (230V)25A · 60m (230V)32A · 60m (230V)40A · 60m (230V)50A · 60m (230V)63A · 60m (230V)80A · 60m (230V)100A · 60m (230V)125A · 60m (230V)160A · 60m (230V)200A · 60m (230V)