Kabelarea för 110 Ampere vid 30 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 110 A över 30 m vid 230V.
Copper Cable (≤3% Drop)35 mm²Drop: 4.04V (1.75%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 4.66V (2.03%)
Voltage at Load226.0 VLine Loss: 443.9 W
Max Power & Breaker25.3 kW110A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 30m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 94.16 V (40.94%) | 135.8 V | 155.32 V (67.53%) | 10357.6 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 56.5 V (24.56%) | 173.5 V | 93.19 V (40.52%) | 6214.6 W | Drop High |
| 4 mm² | 32 A | 25 A | 35.31 V (15.35%) | 194.7 V | 58.24 V (25.32%) | 3884.1 W | Drop High |
| 6 mm² | 41 A | 32 A | 23.54 V (10.23%) | 206.5 V | 38.83 V (16.88%) | 2589.4 W | Drop High |
| 10 mm² | 57 A | 44 A | 14.12 V (6.14%) | 215.9 V | 23.3 V (10.13%) | 1553.6 W | Drop High |
| 16 mm² | 76 A | 59 A | 8.83 V (3.84%) | 221.2 V | 14.56 V (6.33%) | 971.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 5.65 V (2.46%) | 224.4 V | 9.32 V (4.05%) | 621.5 W | Drop High |
| 35 mm² | 125 A | 97 A | 4.04 V (1.75%) | 226.0 V | 6.66 V (2.89%) | 443.9 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 2.82 V (1.23%) | 227.2 V | 4.66 V (2.03%) | 310.7 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 2.02 V (0.88%) | 228.0 V | 3.33 V (1.45%) | 221.9 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 1.49 V (0.65%) | 228.5 V | 2.45 V (1.07%) | 163.5 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 1.18 V (0.51%) | 228.8 V | 1.94 V (0.84%) | 129.5 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.94 V (0.41%) | 229.1 V | 1.55 V (0.68%) | 103.6 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.76 V (0.33%) | 229.2 V | 1.26 V (0.55%) | 84.0 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.59 V (0.26%) | 229.4 V | 0.97 V (0.42%) | 64.7 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.47 V (0.2%) | 229.5 V | 0.78 V (0.34%) | 51.8 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.35 V (0.15%) | 229.6 V | 0.58 V (0.25%) | 38.8 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 110 Ampere vid 30 Meter (230V)
Vilken kabelarea krävs för 110A vid 30 meter (230V)?
För 110 Ampere över 30 meter vid 230V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (4.04V / 1.75%).
Hur stor effekt motsvarar 110A vid 230V?
Det motsvarar 25.3 kW med en rekommenderad säkring på 110A.
Related Lengths & Currents (230V)
110A · 5m (230V)110A · 10m (230V)110A · 15m (230V)110A · 20m (230V)110A · 25m (230V)110A · 35m (230V)110A · 40m (230V)110A · 45m (230V)110A · 50m (230V)110A · 60m (230V)110A · 70m (230V)10A · 30m (230V)16A · 30m (230V)20A · 30m (230V)25A · 30m (230V)32A · 30m (230V)40A · 30m (230V)50A · 30m (230V)63A · 30m (230V)80A · 30m (230V)100A · 30m (230V)125A · 30m (230V)160A · 30m (230V)200A · 30m (230V)