Kabelarea för 110 Ampere vid 25 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 110 A över 25 m vid 230V.
Copper Cable (≤3% Drop)35 mm²Drop: 3.36V (1.46%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 3.88V (1.69%)
Voltage at Load226.6 VLine Loss: 369.9 W
Max Power & Breaker25.3 kW110A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 25m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 78.47 V (34.12%) | 151.5 V | 129.43 V (56.28%) | 8631.3 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 47.08 V (20.47%) | 182.9 V | 77.66 V (33.77%) | 5178.8 W | Drop High |
| 4 mm² | 32 A | 25 A | 29.42 V (12.79%) | 200.6 V | 48.54 V (21.1%) | 3236.7 W | Drop High |
| 6 mm² | 41 A | 32 A | 19.62 V (8.53%) | 210.4 V | 32.36 V (14.07%) | 2157.8 W | Drop High |
| 10 mm² | 57 A | 44 A | 11.77 V (5.12%) | 218.2 V | 19.41 V (8.44%) | 1294.7 W | Drop High |
| 16 mm² | 76 A | 59 A | 7.36 V (3.2%) | 222.6 V | 12.13 V (5.28%) | 809.2 W | Drop High |
| 25 mm² | 101 A | 78 A | 4.71 V (2.05%) | 225.3 V | 7.77 V (3.38%) | 517.9 W | Drop High |
| 35 mm² | 125 A | 97 A | 3.36 V (1.46%) | 226.6 V | 5.55 V (2.41%) | 369.9 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 2.35 V (1.02%) | 227.6 V | 3.88 V (1.69%) | 258.9 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 1.68 V (0.73%) | 228.3 V | 2.77 V (1.21%) | 185.0 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 1.24 V (0.54%) | 228.8 V | 2.04 V (0.89%) | 136.3 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.98 V (0.43%) | 229.0 V | 1.62 V (0.7%) | 107.9 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.78 V (0.34%) | 229.2 V | 1.29 V (0.56%) | 86.3 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.64 V (0.28%) | 229.4 V | 1.05 V (0.46%) | 70.0 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.49 V (0.21%) | 229.5 V | 0.81 V (0.35%) | 53.9 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.39 V (0.17%) | 229.6 V | 0.65 V (0.28%) | 43.2 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.29 V (0.13%) | 229.7 V | 0.49 V (0.21%) | 32.4 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 110 Ampere vid 25 Meter (230V)
Vilken kabelarea krävs för 110A vid 25 meter (230V)?
För 110 Ampere över 25 meter vid 230V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (3.36V / 1.46%).
Hur stor effekt motsvarar 110A vid 230V?
Det motsvarar 25.3 kW med en rekommenderad säkring på 110A.
Related Lengths & Currents (230V)
110A · 5m (230V)110A · 10m (230V)110A · 15m (230V)110A · 20m (230V)110A · 30m (230V)110A · 35m (230V)110A · 40m (230V)110A · 45m (230V)110A · 50m (230V)110A · 60m (230V)110A · 70m (230V)10A · 25m (230V)16A · 25m (230V)20A · 25m (230V)25A · 25m (230V)32A · 25m (230V)40A · 25m (230V)50A · 25m (230V)63A · 25m (230V)80A · 25m (230V)100A · 25m (230V)125A · 25m (230V)160A · 25m (230V)200A · 25m (230V)