Kabelarea för 110 Ampere vid 25 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 110 A över 25 m vid 230V.

Copper Cable (≤3% Drop)35 mm²Drop: 3.36V (1.46%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 3.88V (1.69%)
Voltage at Load226.6 VLine Loss: 369.9 W
Max Power & Breaker25.3 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A78.47 V (34.12%)151.5 V129.43 V (56.28%)8631.3 WDrop High
2.5 mm²24 A18 A47.08 V (20.47%)182.9 V77.66 V (33.77%)5178.8 WDrop High
4 mm²32 A25 A29.42 V (12.79%)200.6 V48.54 V (21.1%)3236.7 WDrop High
6 mm²41 A32 A19.62 V (8.53%)210.4 V32.36 V (14.07%)2157.8 WDrop High
10 mm²57 A44 A11.77 V (5.12%)218.2 V19.41 V (8.44%)1294.7 WDrop High
16 mm²76 A59 A7.36 V (3.2%)222.6 V12.13 V (5.28%)809.2 WDrop High
25 mm²101 A78 A4.71 V (2.05%)225.3 V7.77 V (3.38%)517.9 WDrop High
35 mm²125 A97 A3.36 V (1.46%)226.6 V5.55 V (2.41%)369.9 W✓ OK (≤3%)
50 mm²151 A118 A2.35 V (1.02%)227.6 V3.88 V (1.69%)258.9 W✓ OK (≤3%)
70 mm²192 A150 A1.68 V (0.73%)228.3 V2.77 V (1.21%)185.0 W✓ OK (≤3%)
95 mm²232 A181 A1.24 V (0.54%)228.8 V2.04 V (0.89%)136.3 W✓ OK (≤3%)
120 mm²269 A210 A0.98 V (0.43%)229.0 V1.62 V (0.7%)107.9 W✓ OK (≤3%)
150 mm²309 A241 A0.78 V (0.34%)229.2 V1.29 V (0.56%)86.3 W✓ OK (≤3%)
185 mm²353 A275 A0.64 V (0.28%)229.4 V1.05 V (0.46%)70.0 W✓ OK (≤3%)
240 mm²415 A324 A0.49 V (0.21%)229.5 V0.81 V (0.35%)53.9 W✓ OK (≤3%)
300 mm²477 A372 A0.39 V (0.17%)229.6 V0.65 V (0.28%)43.2 W✓ OK (≤3%)
400 mm²570 A445 A0.29 V (0.13%)229.7 V0.49 V (0.21%)32.4 W✓ OK (≤3%)

FAQ — Kabelarea för 110 Ampere vid 25 Meter (230V)

Vilken kabelarea krävs för 110A vid 25 meter (230V)?

För 110 Ampere över 25 meter vid 230V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (3.36V / 1.46%).

Hur stor effekt motsvarar 110A vid 230V?

Det motsvarar 25.3 kW med en rekommenderad säkring på 110A.