Kabelarea för 425 Ampere vid 120 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 425 A över 120 m vid 230V.

Copper Cable (≤3% Drop)400 mm²Drop: 5.46V (2.37%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 9.0V (3.91%)
Voltage at Load224.5 VLine Loss: 2319.2 W
Max Power & Breaker97.75 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1455.2 V (632.7%)0.0 V2400.4 V (1043.65%)618460.0 WDrop High
2.5 mm²24 A18 A873.12 V (379.62%)0.0 V1440.24 V (626.19%)371076.0 WDrop High
4 mm²32 A25 A545.7 V (237.26%)0.0 V900.15 V (391.37%)231922.5 WDrop High
6 mm²41 A32 A363.8 V (158.17%)0.0 V600.1 V (260.91%)154615.0 WDrop High
10 mm²57 A44 A218.28 V (94.9%)11.7 V360.06 V (156.55%)92769.0 WDrop High
16 mm²76 A59 A136.43 V (59.32%)93.6 V225.04 V (97.84%)57980.6 WDrop High
25 mm²101 A78 A87.31 V (37.96%)142.7 V144.02 V (62.62%)37107.6 WDrop High
35 mm²125 A97 A62.37 V (27.12%)167.6 V102.87 V (44.73%)26505.4 WDrop High
50 mm²151 A118 A43.66 V (18.98%)186.3 V72.01 V (31.31%)18553.8 WDrop High
70 mm²192 A150 A31.18 V (13.56%)198.8 V51.44 V (22.36%)13252.7 WDrop High
95 mm²232 A181 A22.98 V (9.99%)207.0 V37.9 V (16.48%)9765.2 WDrop High
120 mm²269 A210 A18.19 V (7.91%)211.8 V30.0 V (13.05%)7730.8 WDrop High
150 mm²309 A241 A14.55 V (6.33%)215.4 V24.0 V (10.44%)6184.6 WDrop High
185 mm²353 A275 A11.8 V (5.13%)218.2 V19.46 V (8.46%)5014.5 WDrop High
240 mm²415 A324 A9.09 V (3.95%)220.9 V15.0 V (6.52%)3865.4 WDrop High
300 mm²477 A372 A7.28 V (3.16%)222.7 V12.0 V (5.22%)3092.3 W~ ≤5%
400 mm²570 A445 A5.46 V (2.37%)224.5 V9.0 V (3.91%)2319.2 W✓ OK (≤3%)

FAQ — Kabelarea för 425 Ampere vid 120 Meter (230V)

Vilken kabelarea krävs för 425A vid 120 meter (230V)?

För 425 Ampere över 120 meter vid 230V rekommenderas 400 mm² kopparkabel för att hålla spänningsfallet under 3% (5.46V / 2.37%).

Hur stor effekt motsvarar 425A vid 230V?

Det motsvarar 97.75 kW med en rekommenderad säkring på 450A.