Kabelarea för 425 Ampere vid 200 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 425 A över 200 m vid 230V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 4.54V (1.98%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 15.0V (6.52%)
Voltage at Load225.5 VLine Loss: 1932.7 W
Max Power & Breaker97.75 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 200m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2425.33 V (1054.49%)0.0 V4000.67 V (1739.42%)1030766.7 WDrop High
2.5 mm²24 A18 A1455.2 V (632.7%)0.0 V2400.4 V (1043.65%)618460.0 WDrop High
4 mm²32 A25 A909.5 V (395.43%)0.0 V1500.25 V (652.28%)386537.5 WDrop High
6 mm²41 A32 A606.33 V (263.62%)0.0 V1000.17 V (434.86%)257691.7 WDrop High
10 mm²57 A44 A363.8 V (158.17%)0.0 V600.1 V (260.91%)154615.0 WDrop High
16 mm²76 A59 A227.37 V (98.86%)2.6 V375.06 V (163.07%)96634.4 WDrop High
25 mm²101 A78 A145.52 V (63.27%)84.5 V240.04 V (104.37%)61846.0 WDrop High
35 mm²125 A97 A103.94 V (45.19%)126.1 V171.46 V (74.55%)44175.7 WDrop High
50 mm²151 A118 A72.76 V (31.63%)157.2 V120.02 V (52.18%)30923.0 WDrop High
70 mm²192 A150 A51.97 V (22.6%)178.0 V85.73 V (37.27%)22087.9 WDrop High
95 mm²232 A181 A38.29 V (16.65%)191.7 V63.17 V (27.46%)16275.3 WDrop High
120 mm²269 A210 A30.32 V (13.18%)199.7 V50.01 V (21.74%)12884.6 WDrop High
150 mm²309 A241 A24.25 V (10.54%)205.7 V40.01 V (17.39%)10307.7 WDrop High
185 mm²353 A275 A19.66 V (8.55%)210.3 V32.44 V (14.1%)8357.6 WDrop High
240 mm²415 A324 A15.16 V (6.59%)214.8 V25.0 V (10.87%)6442.3 WDrop High
300 mm²477 A372 A12.13 V (5.27%)217.9 V20.0 V (8.7%)5153.8 WDrop High
400 mm²570 A445 A9.09 V (3.95%)220.9 V15.0 V (6.52%)3865.4 W~ ≤5%

FAQ — Kabelarea för 425 Ampere vid 200 Meter (230V)

Vilken kabelarea krävs för 425A vid 200 meter (230V)?

För 425 Ampere över 200 meter vid 230V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (4.54V / 1.98%).

Hur stor effekt motsvarar 425A vid 230V?

Det motsvarar 97.75 kW med en rekommenderad säkring på 450A.