Kabelarea för 450 Ampere vid 90 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 450 A över 90 m vid 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 5.0V (1.25%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.19V (1.55%)
Voltage at Load395.0 VLine Loss: 3900.1 W
Max Power & Breaker311.77 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 450A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1000.78 V (250.19%)0.0 V1650.82 V (412.7%)780030.0 WDrop High
2.5 mm²24 A18 A600.47 V (150.12%)0.0 V990.49 V (247.62%)468018.0 WDrop High
4 mm²32 A25 A375.29 V (93.82%)24.7 V619.06 V (154.76%)292511.2 WDrop High
6 mm²41 A32 A250.19 V (62.55%)149.8 V412.7 V (103.18%)195007.5 WDrop High
10 mm²57 A44 A150.12 V (37.53%)249.9 V247.62 V (61.91%)117004.5 WDrop High
16 mm²76 A59 A93.82 V (23.46%)306.2 V154.76 V (38.69%)73127.8 WDrop High
25 mm²101 A78 A60.05 V (15.01%)340.0 V99.05 V (24.76%)46801.8 WDrop High
35 mm²125 A97 A42.89 V (10.72%)357.1 V70.75 V (17.69%)33429.9 WDrop High
50 mm²151 A118 A30.02 V (7.51%)370.0 V49.52 V (12.38%)23400.9 WDrop High
70 mm²192 A150 A21.45 V (5.36%)378.6 V35.37 V (8.84%)16714.9 WDrop High
95 mm²232 A181 A15.8 V (3.95%)384.2 V26.07 V (6.52%)12316.3 WDrop High
120 mm²269 A210 A12.51 V (3.13%)387.5 V20.64 V (5.16%)9750.4 WDrop High
150 mm²309 A241 A10.01 V (2.5%)390.0 V16.51 V (4.13%)7800.3 WDrop High
185 mm²353 A275 A8.11 V (2.03%)391.9 V13.39 V (3.35%)6324.6 WDrop High
240 mm²415 A324 A6.25 V (1.56%)393.7 V10.32 V (2.58%)4875.2 WDrop High
300 mm²477 A372 A5.0 V (1.25%)395.0 V8.25 V (2.06%)3900.1 W✓ OK (≤3%)
400 mm²570 A445 A3.75 V (0.94%)396.2 V6.19 V (1.55%)2925.1 W✓ OK (≤3%)

FAQ — Kabelarea för 450 Ampere vid 90 Meter (400V)

Vilken kabelarea krävs för 450A vid 90 meter (400V)?

För 450 Ampere över 90 meter vid 400V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (5.0V / 1.25%).

Hur stor effekt motsvarar 450A vid 400V?

Det motsvarar 311.77 kW med en rekommenderad säkring på 450A.