Kabelarea för 475 Ampere vid 120 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 475 A över 120 m vid 230V.

Copper Cable (≤3% Drop)400 mm²Drop: 6.1V (2.65%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 10.06V (4.37%)
Voltage at Load223.9 VLine Loss: 2897.0 W
Max Power & Breaker109.25 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1626.4 V (707.13%)0.0 V2682.8 V (1166.43%)772540.0 WDrop High
2.5 mm²24 A18 A975.84 V (424.28%)0.0 V1609.68 V (699.86%)463524.0 WDrop High
4 mm²32 A25 A609.9 V (265.17%)0.0 V1006.05 V (437.41%)289702.5 WDrop High
6 mm²41 A32 A406.6 V (176.78%)0.0 V670.7 V (291.61%)193135.0 WDrop High
10 mm²57 A44 A243.96 V (106.07%)0.0 V402.42 V (174.97%)115881.0 WDrop High
16 mm²76 A59 A152.47 V (66.29%)77.5 V251.51 V (109.35%)72425.6 WDrop High
25 mm²101 A78 A97.58 V (42.43%)132.4 V160.97 V (69.99%)46352.4 WDrop High
35 mm²125 A97 A69.7 V (30.31%)160.3 V114.98 V (49.99%)33108.9 WDrop High
50 mm²151 A118 A48.79 V (21.21%)181.2 V80.48 V (34.99%)23176.2 WDrop High
70 mm²192 A150 A34.85 V (15.15%)195.1 V57.49 V (25.0%)16554.4 WDrop High
95 mm²232 A181 A25.68 V (11.17%)204.3 V42.36 V (18.42%)12198.0 WDrop High
120 mm²269 A210 A20.33 V (8.84%)209.7 V33.53 V (14.58%)9656.8 WDrop High
150 mm²309 A241 A16.26 V (7.07%)213.7 V26.83 V (11.66%)7725.4 WDrop High
185 mm²353 A275 A13.19 V (5.73%)216.8 V21.75 V (9.46%)6263.8 WDrop High
240 mm²415 A324 A10.16 V (4.42%)219.8 V16.77 V (7.29%)4828.4 WDrop High
300 mm²477 A372 A8.13 V (3.54%)221.9 V13.41 V (5.83%)3862.7 W~ ≤5%
400 mm²570 A445 A6.1 V (2.65%)223.9 V10.06 V (4.37%)2897.0 W✓ OK (≤3%)

FAQ — Kabelarea för 475 Ampere vid 120 Meter (230V)

Vilken kabelarea krävs för 475A vid 120 meter (230V)?

För 475 Ampere över 120 meter vid 230V rekommenderas 400 mm² kopparkabel för att hålla spänningsfallet under 3% (6.1V / 2.65%).

Hur stor effekt motsvarar 475A vid 230V?

Det motsvarar 109.25 kW med en rekommenderad säkring på 500A.