Kabelarea för 550 Ampere vid 120 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 550 A över 120 m vid 400V.

Copper Cable (≤3% Drop)400 mm²Drop: 6.12V (1.53%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 10.09V (2.52%)
Voltage at Load393.9 VLine Loss: 5826.2 W
Max Power & Breaker381.05 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1630.9 V (407.72%)0.0 V2690.22 V (672.56%)1553640.0 WDrop High
2.5 mm²24 A18 A978.54 V (244.63%)0.0 V1614.13 V (403.53%)932184.0 WDrop High
4 mm²32 A25 A611.59 V (152.9%)0.0 V1008.83 V (252.21%)582615.0 WDrop High
6 mm²41 A32 A407.72 V (101.93%)0.0 V672.56 V (168.14%)388410.0 WDrop High
10 mm²57 A44 A244.63 V (61.16%)155.4 V403.53 V (100.88%)233046.0 WDrop High
16 mm²76 A59 A152.9 V (38.22%)247.1 V252.21 V (63.05%)145653.8 WDrop High
25 mm²101 A78 A97.85 V (24.46%)302.1 V161.41 V (40.35%)93218.4 WDrop High
35 mm²125 A97 A69.9 V (17.47%)330.1 V115.3 V (28.82%)66584.6 WDrop High
50 mm²151 A118 A48.93 V (12.23%)351.1 V80.71 V (20.18%)46609.2 WDrop High
70 mm²192 A150 A34.95 V (8.74%)365.1 V57.65 V (14.41%)33292.3 WDrop High
95 mm²232 A181 A25.75 V (6.44%)374.2 V42.48 V (10.62%)24531.2 WDrop High
120 mm²269 A210 A20.39 V (5.1%)379.6 V33.63 V (8.41%)19420.5 WDrop High
150 mm²309 A241 A16.31 V (4.08%)383.7 V26.9 V (6.73%)15536.4 WDrop High
185 mm²353 A275 A13.22 V (3.31%)386.8 V21.81 V (5.45%)12597.1 WDrop High
240 mm²415 A324 A10.19 V (2.55%)389.8 V16.81 V (4.2%)9710.2 WDrop High
300 mm²477 A372 A8.15 V (2.04%)391.8 V13.45 V (3.36%)7768.2 WDrop High
400 mm²570 A445 A6.12 V (1.53%)393.9 V10.09 V (2.52%)5826.2 W✓ OK (≤3%)

FAQ — Kabelarea för 550 Ampere vid 120 Meter (400V)

Vilken kabelarea krävs för 550A vid 120 meter (400V)?

För 550 Ampere över 120 meter vid 400V rekommenderas 400 mm² kopparkabel för att hålla spänningsfallet under 3% (6.12V / 1.53%).

Hur stor effekt motsvarar 550A vid 400V?

Det motsvarar 381.05 kW med en rekommenderad säkring på 600A.