Kabelarea för 700 Ampere vid 175 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 700 A över 175 m vid 400V.
Copper Cable (≤3% Drop)2× 400 mm²Drop: 5.67V (1.42%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 18.72V (4.68%)
Voltage at Load394.3 VLine Loss: 6881.4 W
Max Power & Breaker484.97 kW700A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 175m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 3027.05 V (756.76%) | 0.0 V | 4993.21 V (1248.3%) | 3670100.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 1816.23 V (454.06%) | 0.0 V | 2995.93 V (748.98%) | 2202060.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 1135.14 V (283.79%) | 0.0 V | 1872.46 V (468.11%) | 1376287.5 W | Drop High |
| 6 mm² | 41 A | 32 A | 756.76 V (189.19%) | 0.0 V | 1248.3 V (312.08%) | 917525.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 454.06 V (113.51%) | 0.0 V | 748.98 V (187.25%) | 550515.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 283.79 V (70.95%) | 116.2 V | 468.11 V (117.03%) | 344071.9 W | Drop High |
| 25 mm² | 101 A | 78 A | 181.62 V (45.41%) | 218.4 V | 299.59 V (74.9%) | 220206.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 129.73 V (32.43%) | 270.3 V | 213.99 V (53.5%) | 157290.0 W | Drop High |
| 50 mm² | 151 A | 118 A | 90.81 V (22.7%) | 309.2 V | 149.8 V (37.45%) | 110103.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 64.87 V (16.22%) | 335.1 V | 107.0 V (26.75%) | 78645.0 W | Drop High |
| 95 mm² | 232 A | 181 A | 47.8 V (11.95%) | 352.2 V | 78.84 V (19.71%) | 57948.9 W | Drop High |
| 120 mm² | 269 A | 210 A | 37.84 V (9.46%) | 362.2 V | 62.42 V (15.6%) | 45876.2 W | Drop High |
| 150 mm² | 309 A | 241 A | 30.27 V (7.57%) | 369.7 V | 49.93 V (12.48%) | 36701.0 W | Drop High |
| 185 mm² | 353 A | 275 A | 24.54 V (6.14%) | 375.5 V | 40.49 V (10.12%) | 29757.6 W | Drop High |
| 240 mm² | 415 A | 324 A | 18.92 V (4.73%) | 381.1 V | 31.21 V (7.8%) | 22938.1 W | Drop High |
| 300 mm² | 477 A | 372 A | 15.14 V (3.78%) | 384.9 V | 24.97 V (6.24%) | 18350.5 W | Drop High |
| 400 mm² | 570 A | 445 A | 11.35 V (2.84%) | 388.6 V | 18.72 V (4.68%) | 13762.9 W | Drop High |
FAQ — Kabelarea för 700 Ampere vid 175 Meter (400V)
Vilken kabelarea krävs för 700A vid 175 meter (400V)?
För 700 Ampere över 175 meter vid 400V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (5.67V / 1.42%).
Hur stor effekt motsvarar 700A vid 400V?
Det motsvarar 484.97 kW med en rekommenderad säkring på 700A.
Related Lengths & Currents (400V)
700A · 5m (400V)700A · 10m (400V)700A · 15m (400V)700A · 20m (400V)700A · 25m (400V)700A · 30m (400V)700A · 35m (400V)700A · 40m (400V)700A · 45m (400V)700A · 50m (400V)700A · 60m (400V)700A · 70m (400V)10A · 175m (400V)16A · 175m (400V)20A · 175m (400V)25A · 175m (400V)32A · 175m (400V)40A · 175m (400V)50A · 175m (400V)63A · 175m (400V)80A · 175m (400V)100A · 175m (400V)125A · 175m (400V)160A · 175m (400V)200A · 175m (400V)