⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

10 Amp Wire Size at 275 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 10 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)12 AWG3.31 mm² · Drop: 1.96%
Aluminum Wire (≤3% Drop)10 AWGDrop: 9.74V (2.03%)
Voltage at Load End470.6 VLoss: 9.39 V (162.6 W)
Power & Breaker (125%)8.31 kW13A Breaker Recommended

All AWG & kcmil Wire Gauges for 10 Amps at 275 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A14.94 V (3.11%)465.1 V24.64 V (5.13%)258.7 W~ ≤5%
12 AWG3.31 mm²20 A9.39 V (1.96%)470.6 V15.48 V (3.23%)162.6 W✓ PASS (≤3%)
10 AWG5.26 mm²30 A5.91 V (1.23%)474.1 V9.74 V (2.03%)102.3 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A3.71 V (0.77%)476.3 V6.12 V (1.28%)64.3 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A2.34 V (0.49%)477.7 V3.85 V (0.8%)40.5 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.47 V (0.31%)478.5 V2.42 V (0.5%)25.4 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.16 V (0.24%)478.8 V1.92 V (0.4%)20.2 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.92 V (0.19%)479.1 V1.52 V (0.32%)16.0 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.73 V (0.15%)479.3 V1.21 V (0.25%)12.7 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.58 V (0.12%)479.4 V0.96 V (0.2%)10.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.46 V (0.1%)479.5 V0.76 V (0.16%)8.0 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.37 V (0.08%)479.6 V0.6 V (0.13%)6.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.29 V (0.06%)479.7 V0.48 V (0.1%)5.0 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.25 V (0.05%)479.8 V0.4 V (0.08%)4.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.2 V (0.04%)479.8 V0.34 V (0.07%)3.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.18 V (0.04%)479.8 V0.29 V (0.06%)3.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.15 V (0.03%)479.8 V0.25 V (0.05%)2.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.12 V (0.03%)479.9 V0.2 V (0.04%)2.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.1 V (0.02%)479.9 V0.17 V (0.04%)1.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.08 V (0.02%)479.9 V0.13 V (0.03%)1.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.06 V (0.01%)479.9 V0.1 V (0.02%)1.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 10 amps at 275 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 10A load over 275 feet one-way at 480V (3-Phase), you need 12 AWG copper wire. This produces a voltage drop of 9.39V (1.96%) and delivers 470.6V at the load.

What size aluminum wire is required for 10 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 10 AWG to maintain voltage drop at 9.74V (2.03%).

What breaker size is needed for a 10A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (10A × 1.25 = 12.5A), which corresponds to a standard 13A circuit breaker.