🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

1000 Amp Wire Size at 1000 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 1000 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.33%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 36.78V (7.66%)
Voltage at Load End468.9 VLoss: 11.15 V (19309.4 W)
Power & Breaker (125%)831.38 kW1600A Breaker Recommended

All AWG & kcmil Wire Gauges for 1000 Amps at 1000 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A5431.58 V (1131.58%)0.0 V8959.57 V (1866.58%)9407769.2 WDrop/Amp High
12 AWG3.31 mm²20 A3413.2 V (711.08%)0.0 V5630.18 V (1172.95%)5911830.8 WDrop/Amp High
10 AWG5.26 mm²30 A2147.85 V (447.47%)0.0 V3542.95 V (738.11%)3720182.5 WDrop/Amp High
8 AWG8.37 mm²50 A1349.78 V (281.2%)0.0 V2226.51 V (463.86%)2337892.5 WDrop/Amp High
6 AWG13.3 mm²65 A849.45 V (176.97%)0.0 V1401.2 V (291.92%)1471290.2 WDrop/Amp High
4 AWG21.15 mm²85 A534.17 V (111.29%)0.0 V881.13 V (183.57%)925208.5 WDrop/Amp High
3 AWG26.67 mm²100 A423.61 V (88.25%)56.4 V698.76 V (145.57%)733714.3 WDrop/Amp High
2 AWG33.62 mm²115 A336.04 V (70.01%)144.0 V554.31 V (115.48%)582039.3 WDrop/Amp High
1 AWG42.41 mm²130 A266.39 V (55.5%)213.6 V439.42 V (91.55%)461404.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A211.21 V (44.0%)268.8 V348.4 V (72.58%)365828.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A167.55 V (34.91%)312.5 V276.37 V (57.58%)290199.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A132.9 V (27.69%)347.1 V219.22 V (45.67%)230186.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A105.39 V (21.96%)374.6 V173.84 V (36.22%)182538.8 WDrop/Amp High
250 kcmil126.7 mm²255 A89.17 V (18.58%)390.8 V147.09 V (30.64%)154444.8 WDrop/Amp High
300 kcmil152.0 mm²285 A74.33 V (15.48%)405.7 V122.6 V (25.54%)128737.9 WDrop/Amp High
350 kcmil177.3 mm²310 A63.72 V (13.28%)416.3 V105.11 V (21.9%)110367.5 WDrop/Amp High
400 kcmil202.7 mm²335 A55.74 V (11.61%)424.3 V91.94 V (19.15%)96537.5 WDrop/Amp High
500 kcmil253.4 mm²380 A44.58 V (9.29%)435.4 V73.54 V (15.32%)77222.4 WDrop/Amp High
600 kcmil304.0 mm²420 A37.16 V (7.74%)442.8 V61.3 V (12.77%)64368.9 WDrop/Amp High
750 kcmil380.0 mm²475 A29.73 V (6.19%)450.3 V49.04 V (10.22%)51495.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A22.3 V (4.65%)457.7 V36.78 V (7.66%)38618.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 1000 amps at 1000 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 1000A load over 1000 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 11.15V (2.33%) and delivers 468.9V at the load.

What size aluminum wire is required for 1000 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 36.78V (7.66%).

What breaker size is needed for a 1000A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (1000A × 1.25 = 1250.0A), which corresponds to a standard 1600A circuit breaker.