110 Amp Wire Size at 200 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 200 ft (61.0 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 2.81%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 3.11V (2.6%)
Voltage at Load End116.6 VLoss: 3.38 V (371.4 W)
Power & Breaker (125%)13.2 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 200 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A137.98 V (114.98%)0.0 V227.6 V (189.67%)15177.9 WDrop/Amp High
12 AWG3.31 mm²20 A86.71 V (72.26%)33.3 V143.03 V (119.19%)9537.8 WDrop/Amp High
10 AWG5.26 mm²30 A54.56 V (45.47%)65.4 V90.0 V (75.0%)6001.9 WDrop/Amp High
8 AWG8.37 mm²50 A34.29 V (28.57%)85.7 V56.56 V (47.13%)3771.8 WDrop/Amp High
6 AWG13.3 mm²65 A21.58 V (17.98%)98.4 V35.6 V (29.66%)2373.7 WDrop/Amp High
4 AWG21.15 mm²85 A13.57 V (11.31%)106.4 V22.38 V (18.65%)1492.7 WDrop/Amp High
3 AWG26.67 mm²100 A10.76 V (8.97%)109.2 V17.75 V (14.79%)1183.7 WDrop/Amp High
2 AWG33.62 mm²115 A8.54 V (7.11%)111.5 V14.08 V (11.73%)939.0 WDrop/Amp High
1 AWG42.41 mm²130 A6.77 V (5.64%)113.2 V11.16 V (9.3%)744.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.37 V (4.47%)114.6 V8.85 V (7.38%)590.2 W~ ≤5%
2/0 AWG67.43 mm²175 A4.26 V (3.55%)115.7 V7.02 V (5.85%)468.2 W~ ≤5%
3/0 AWG85.01 mm²200 A3.38 V (2.81%)116.6 V5.57 V (4.64%)371.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.68 V (2.23%)117.3 V4.42 V (3.68%)294.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.27 V (1.89%)117.7 V3.74 V (3.11%)249.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.89 V (1.57%)118.1 V3.11 V (2.6%)207.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.62 V (1.35%)118.4 V2.67 V (2.23%)178.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.42 V (1.18%)118.6 V2.34 V (1.95%)155.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.13 V (0.94%)118.9 V1.87 V (1.56%)124.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.94 V (0.79%)119.1 V1.56 V (1.3%)103.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.76 V (0.63%)119.2 V1.25 V (1.04%)83.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.57 V (0.47%)119.4 V0.93 V (0.78%)62.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 200 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 200 feet one-way at 120V (1-Phase), you need 3/0 AWG copper wire. This produces a voltage drop of 3.38V (2.81%) and delivers 116.6V at the load.

What size aluminum wire is required for 110 amps at 200 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 3.11V (2.6%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.