🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 250 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 2.79%
Aluminum Wire (≤3% Drop)350 kcmilDrop: 3.34V (2.78%)
Voltage at Load End116.7 VLoss: 3.35 V (368.1 W)
Power & Breaker (125%)13.2 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 250 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A172.48 V (143.73%)0.0 V284.5 V (237.09%)18972.3 WDrop/Amp High
12 AWG3.31 mm²20 A108.38 V (90.32%)11.6 V178.78 V (148.99%)11922.2 WDrop/Amp High
10 AWG5.26 mm²30 A68.2 V (56.84%)51.8 V112.5 V (93.75%)7502.4 WDrop/Amp High
8 AWG8.37 mm²50 A42.86 V (35.72%)77.1 V70.7 V (58.92%)4714.7 WDrop/Amp High
6 AWG13.3 mm²65 A26.97 V (22.48%)93.0 V44.49 V (37.08%)2967.1 WDrop/Amp High
4 AWG21.15 mm²85 A16.96 V (14.14%)103.0 V27.98 V (23.32%)1865.8 WDrop/Amp High
3 AWG26.67 mm²100 A13.45 V (11.21%)106.5 V22.19 V (18.49%)1479.7 WDrop/Amp High
2 AWG33.62 mm²115 A10.67 V (8.89%)109.3 V17.6 V (14.67%)1173.8 WDrop/Amp High
1 AWG42.41 mm²130 A8.46 V (7.05%)111.5 V13.95 V (11.63%)930.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A6.71 V (5.59%)113.3 V11.06 V (9.22%)737.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.32 V (4.43%)114.7 V8.78 V (7.31%)585.2 W~ ≤5%
3/0 AWG85.01 mm²200 A4.22 V (3.52%)115.8 V6.96 V (5.8%)464.2 W~ ≤5%
4/0 AWG107.2 mm²230 A3.35 V (2.79%)116.7 V5.52 V (4.6%)368.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.83 V (2.36%)117.2 V4.67 V (3.89%)311.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.36 V (1.97%)117.6 V3.89 V (3.24%)259.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.02 V (1.69%)118.0 V3.34 V (2.78%)222.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.77 V (1.47%)118.2 V2.92 V (2.43%)194.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.42 V (1.18%)118.6 V2.34 V (1.95%)155.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.18 V (0.98%)118.8 V1.95 V (1.62%)129.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.94 V (0.79%)119.1 V1.56 V (1.3%)103.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.71 V (0.59%)119.3 V1.17 V (0.97%)77.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 250 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 250 feet one-way at 120V (1-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 3.35V (2.79%) and delivers 116.7V at the load.

What size aluminum wire is required for 110 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 350 kcmil to maintain voltage drop at 3.34V (2.78%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.