🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 300 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 300 ft (91.4 m) one-way run.

Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 2.83%
Aluminum Wire (≤3% Drop)400 kcmilDrop: 3.5V (2.92%)
Voltage at Load End116.6 VLoss: 3.4 V (373.8 W)
Power & Breaker (125%)13.2 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 300 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A206.97 V (172.48%)0.0 V341.41 V (284.5%)22766.8 WDrop/Amp High
12 AWG3.31 mm²20 A130.06 V (108.38%)0.0 V214.54 V (178.78%)14306.6 WDrop/Amp High
10 AWG5.26 mm²30 A81.84 V (68.2%)38.2 V135.0 V (112.5%)9002.8 WDrop/Amp High
8 AWG8.37 mm²50 A51.43 V (42.86%)68.6 V84.84 V (70.7%)5657.7 WDrop/Amp High
6 AWG13.3 mm²65 A32.37 V (26.97%)87.6 V53.39 V (44.49%)3560.5 WDrop/Amp High
4 AWG21.15 mm²85 A20.35 V (16.96%)99.6 V33.58 V (27.98%)2239.0 WDrop/Amp High
3 AWG26.67 mm²100 A16.14 V (13.45%)103.9 V26.63 V (22.19%)1775.6 WDrop/Amp High
2 AWG33.62 mm²115 A12.8 V (10.67%)107.2 V21.12 V (17.6%)1408.5 WDrop/Amp High
1 AWG42.41 mm²130 A10.15 V (8.46%)109.8 V16.74 V (13.95%)1116.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A8.05 V (6.71%)112.0 V13.28 V (11.06%)885.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.38 V (5.32%)113.6 V10.53 V (8.78%)702.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.06 V (4.22%)114.9 V8.35 V (6.96%)557.1 W~ ≤5%
4/0 AWG107.2 mm²230 A4.02 V (3.35%)116.0 V6.62 V (5.52%)441.7 W~ ≤5%
250 kcmil126.7 mm²255 A3.4 V (2.83%)116.6 V5.6 V (4.67%)373.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.83 V (2.36%)117.2 V4.67 V (3.89%)311.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.43 V (2.02%)117.6 V4.01 V (3.34%)267.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.12 V (1.77%)117.9 V3.5 V (2.92%)233.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.7 V (1.42%)118.3 V2.8 V (2.34%)186.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.42 V (1.18%)118.6 V2.34 V (1.95%)155.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.13 V (0.94%)118.9 V1.87 V (1.56%)124.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.85 V (0.71%)119.2 V1.4 V (1.17%)93.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 300 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 300 feet one-way at 120V (1-Phase), you need 250 kcmil copper wire. This produces a voltage drop of 3.4V (2.83%) and delivers 116.6V at the load.

What size aluminum wire is required for 110 amps at 300 feet?

Using aluminum conductors (75°C rating), you should use 400 kcmil to maintain voltage drop at 3.5V (2.92%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.