🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 400 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 2.44%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 12.16V (2.53%)
Voltage at Load End468.3 VLoss: 11.72 V (2233.2 W)
Power & Breaker (125%)91.45 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 400 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A238.99 V (49.79%)241.0 V394.22 V (82.13%)45533.6 WDrop/Amp High
12 AWG3.31 mm²20 A150.18 V (31.29%)329.8 V247.73 V (51.61%)28613.3 WDrop/Amp High
10 AWG5.26 mm²30 A94.51 V (19.69%)385.5 V155.89 V (32.48%)18005.7 WDrop/Amp High
8 AWG8.37 mm²50 A59.39 V (12.37%)420.6 V97.97 V (20.41%)11315.4 WDrop/Amp High
6 AWG13.3 mm²65 A37.38 V (7.79%)442.6 V61.65 V (12.84%)7121.0 WDrop/Amp High
4 AWG21.15 mm²85 A23.5 V (4.9%)456.5 V38.77 V (8.08%)4478.0 WDrop/Amp High
3 AWG26.67 mm²100 A18.64 V (3.88%)461.4 V30.75 V (6.41%)3551.2 WDrop/Amp High
2 AWG33.62 mm²115 A14.79 V (3.08%)465.2 V24.39 V (5.08%)2817.1 W~ ≤5%
1 AWG42.41 mm²130 A11.72 V (2.44%)468.3 V19.33 V (4.03%)2233.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A9.29 V (1.94%)470.7 V15.33 V (3.19%)1770.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A7.37 V (1.54%)472.6 V12.16 V (2.53%)1404.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A5.85 V (1.22%)474.2 V9.65 V (2.01%)1114.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A4.64 V (0.97%)475.4 V7.65 V (1.59%)883.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A3.92 V (0.82%)476.1 V6.47 V (1.35%)747.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A3.27 V (0.68%)476.7 V5.39 V (1.12%)623.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.8 V (0.58%)477.2 V4.62 V (0.96%)534.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.45 V (0.51%)477.5 V4.05 V (0.84%)467.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.96 V (0.41%)478.0 V3.24 V (0.67%)373.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.64 V (0.34%)478.4 V2.7 V (0.56%)311.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.31 V (0.27%)478.7 V2.16 V (0.45%)249.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.98 V (0.2%)479.0 V1.62 V (0.34%)186.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 400 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 400 feet one-way at 480V (3-Phase), you need 1 AWG copper wire. This produces a voltage drop of 11.72V (2.44%) and delivers 468.3V at the load.

What size aluminum wire is required for 110 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 12.16V (2.53%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.