🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 450 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 2.75%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 13.68V (2.85%)
Voltage at Load End466.8 VLoss: 13.19 V (2512.3 W)
Power & Breaker (125%)91.45 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 450 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A268.86 V (56.01%)211.1 V443.5 V (92.4%)51225.3 WDrop/Amp High
12 AWG3.31 mm²20 A168.95 V (35.2%)311.0 V278.69 V (58.06%)32189.9 WDrop/Amp High
10 AWG5.26 mm²30 A106.32 V (22.15%)373.7 V175.38 V (36.54%)20256.4 WDrop/Amp High
8 AWG8.37 mm²50 A66.81 V (13.92%)413.2 V110.21 V (22.96%)12729.8 WDrop/Amp High
6 AWG13.3 mm²65 A42.05 V (8.76%)438.0 V69.36 V (14.45%)8011.2 WDrop/Amp High
4 AWG21.15 mm²85 A26.44 V (5.51%)453.6 V43.62 V (9.09%)5037.8 WDrop/Amp High
3 AWG26.67 mm²100 A20.97 V (4.37%)459.0 V34.59 V (7.21%)3995.1 WDrop/Amp High
2 AWG33.62 mm²115 A16.63 V (3.47%)463.4 V27.44 V (5.72%)3169.2 W~ ≤5%
1 AWG42.41 mm²130 A13.19 V (2.75%)466.8 V21.75 V (4.53%)2512.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A10.45 V (2.18%)469.5 V17.25 V (3.59%)1991.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A8.29 V (1.73%)471.7 V13.68 V (2.85%)1580.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A6.58 V (1.37%)473.4 V10.85 V (2.26%)1253.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A5.22 V (1.09%)474.8 V8.61 V (1.79%)993.9 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A4.41 V (0.92%)475.6 V7.28 V (1.52%)841.0 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A3.68 V (0.77%)476.3 V6.07 V (1.26%)701.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.15 V (0.66%)476.8 V5.2 V (1.08%)601.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.76 V (0.57%)477.2 V4.55 V (0.95%)525.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.21 V (0.46%)477.8 V3.64 V (0.76%)420.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.84 V (0.38%)478.2 V3.03 V (0.63%)350.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.47 V (0.31%)478.5 V2.43 V (0.51%)280.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.1 V (0.23%)478.9 V1.82 V (0.38%)210.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 450 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 450 feet one-way at 480V (3-Phase), you need 1 AWG copper wire. This produces a voltage drop of 13.19V (2.75%) and delivers 466.8V at the load.

What size aluminum wire is required for 110 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 13.68V (2.85%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.