🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 500 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)4× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.95%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.34V (19.46%)
Voltage at Load End11.7 VLoss: 0.35 V (39.0 W)
Power & Breaker (125%)1.32 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 500 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A344.95 V (2874.6%)0.0 V569.01 V (4741.74%)37944.7 WDrop/Amp High
12 AWG3.31 mm²20 A216.77 V (1806.39%)0.0 V357.56 V (2979.7%)23844.4 WDrop/Amp High
10 AWG5.26 mm²30 A136.41 V (1136.72%)0.0 V225.01 V (1875.06%)15004.7 WDrop/Amp High
8 AWG8.37 mm²50 A85.72 V (714.36%)0.0 V141.4 V (1178.35%)9429.5 WDrop/Amp High
6 AWG13.3 mm²65 A53.95 V (449.56%)0.0 V88.99 V (741.57%)5934.2 WDrop/Amp High
4 AWG21.15 mm²85 A33.92 V (282.7%)0.0 V55.96 V (466.33%)3731.7 WDrop/Amp High
3 AWG26.67 mm²100 A26.9 V (224.19%)0.0 V44.38 V (369.81%)2959.3 WDrop/Amp High
2 AWG33.62 mm²115 A21.34 V (177.85%)0.0 V35.2 V (293.36%)2347.6 WDrop/Amp High
1 AWG42.41 mm²130 A16.92 V (140.98%)0.0 V27.91 V (232.56%)1861.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.41 V (111.78%)0.0 V22.13 V (184.39%)1475.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A10.64 V (88.67%)1.4 V17.55 V (146.27%)1170.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.44 V (70.33%)3.6 V13.92 V (116.02%)928.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.69 V (55.78%)5.3 V11.04 V (92.0%)736.2 WDrop/Amp High
250 kcmil126.7 mm²255 A5.66 V (47.19%)6.3 V9.34 V (77.84%)622.9 WDrop/Amp High
300 kcmil152.0 mm²285 A4.72 V (39.34%)7.3 V7.79 V (64.89%)519.2 WDrop/Amp High
350 kcmil177.3 mm²310 A4.05 V (33.72%)8.0 V6.68 V (55.63%)445.1 WDrop/Amp High
400 kcmil202.7 mm²335 A3.54 V (29.5%)8.5 V5.84 V (48.66%)389.4 WDrop/Amp High
500 kcmil253.4 mm²380 A2.83 V (23.6%)9.2 V4.67 V (38.92%)311.5 WDrop/Amp High
600 kcmil304.0 mm²420 A2.36 V (19.67%)9.6 V3.89 V (32.44%)259.6 WDrop/Amp High
750 kcmil380.0 mm²475 A1.89 V (15.73%)10.1 V3.11 V (25.95%)207.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.42 V (11.8%)10.6 V2.34 V (19.46%)155.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 500 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 500 feet one-way at 12V (DC), you need 4× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.35V (2.95%) and delivers 11.7V at the load.

What size aluminum wire is required for 110 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.34V (19.46%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.