🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 800 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.52%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.74V (3.11%)
Voltage at Load End117.0 VLoss: 3.02 V (332.3 W)
Power & Breaker (125%)13.2 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 800 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A551.92 V (459.94%)0.0 V910.41 V (758.68%)60711.5 WDrop/Amp High
12 AWG3.31 mm²20 A346.83 V (289.02%)0.0 V572.1 V (476.75%)38151.0 WDrop/Amp High
10 AWG5.26 mm²30 A218.25 V (181.88%)0.0 V360.01 V (300.01%)24007.6 WDrop/Amp High
8 AWG8.37 mm²50 A137.16 V (114.3%)0.0 V226.24 V (188.54%)15087.2 WDrop/Amp High
6 AWG13.3 mm²65 A86.32 V (71.93%)33.7 V142.38 V (118.65%)9494.7 WDrop/Amp High
4 AWG21.15 mm²85 A54.28 V (45.23%)65.7 V89.53 V (74.61%)5970.7 WDrop/Amp High
3 AWG26.67 mm²100 A43.04 V (35.87%)77.0 V71.0 V (59.17%)4734.9 WDrop/Amp High
2 AWG33.62 mm²115 A34.15 V (28.46%)85.9 V56.33 V (46.94%)3756.1 WDrop/Amp High
1 AWG42.41 mm²130 A27.07 V (22.56%)92.9 V44.65 V (37.21%)2977.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A21.46 V (17.88%)98.5 V35.4 V (29.5%)2360.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A17.03 V (14.19%)103.0 V28.08 V (23.4%)1872.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A13.5 V (11.25%)106.5 V22.28 V (18.56%)1485.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.71 V (8.92%)109.3 V17.66 V (14.72%)1178.0 WDrop/Amp High
250 kcmil126.7 mm²255 A9.06 V (7.55%)110.9 V14.95 V (12.46%)996.7 WDrop/Amp High
300 kcmil152.0 mm²285 A7.55 V (6.29%)112.4 V12.46 V (10.38%)830.8 WDrop/Amp High
350 kcmil177.3 mm²310 A6.47 V (5.4%)113.5 V10.68 V (8.9%)712.2 WDrop/Amp High
400 kcmil202.7 mm²335 A5.66 V (4.72%)114.3 V9.34 V (7.79%)623.0 W~ ≤5%
500 kcmil253.4 mm²380 A4.53 V (3.78%)115.5 V7.47 V (6.23%)498.3 W~ ≤5%
600 kcmil304.0 mm²420 A3.78 V (3.15%)116.2 V6.23 V (5.19%)415.4 W~ ≤5%
750 kcmil380.0 mm²475 A3.02 V (2.52%)117.0 V4.98 V (4.15%)332.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.27 V (1.89%)117.7 V3.74 V (3.11%)249.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 800 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 800 feet one-way at 120V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 3.02V (2.52%) and delivers 117.0V at the load.

What size aluminum wire is required for 110 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.74V (3.11%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.