🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 800 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)350 kcmil177.3 mm² · Drop: 2.7%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 6.23V (2.6%)
Voltage at Load End233.5 VLoss: 6.47 V (712.2 W)
Power & Breaker (125%)26.4 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 800 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A551.92 V (229.97%)0.0 V910.41 V (379.34%)60711.5 WDrop/Amp High
12 AWG3.31 mm²20 A346.83 V (144.51%)0.0 V572.1 V (238.38%)38151.0 WDrop/Amp High
10 AWG5.26 mm²30 A218.25 V (90.94%)21.7 V360.01 V (150.0%)24007.6 WDrop/Amp High
8 AWG8.37 mm²50 A137.16 V (57.15%)102.8 V226.24 V (94.27%)15087.2 WDrop/Amp High
6 AWG13.3 mm²65 A86.32 V (35.96%)153.7 V142.38 V (59.33%)9494.7 WDrop/Amp High
4 AWG21.15 mm²85 A54.28 V (22.62%)185.7 V89.53 V (37.31%)5970.7 WDrop/Amp High
3 AWG26.67 mm²100 A43.04 V (17.94%)197.0 V71.0 V (29.58%)4734.9 WDrop/Amp High
2 AWG33.62 mm²115 A34.15 V (14.23%)205.9 V56.33 V (23.47%)3756.1 WDrop/Amp High
1 AWG42.41 mm²130 A27.07 V (11.28%)212.9 V44.65 V (18.6%)2977.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A21.46 V (8.94%)218.5 V35.4 V (14.75%)2360.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A17.03 V (7.09%)223.0 V28.08 V (11.7%)1872.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A13.5 V (5.63%)226.5 V22.28 V (9.28%)1485.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.71 V (4.46%)229.3 V17.66 V (7.36%)1178.0 W~ ≤5%
250 kcmil126.7 mm²255 A9.06 V (3.78%)230.9 V14.95 V (6.23%)996.7 W~ ≤5%
300 kcmil152.0 mm²285 A7.55 V (3.15%)232.4 V12.46 V (5.19%)830.8 W~ ≤5%
350 kcmil177.3 mm²310 A6.47 V (2.7%)233.5 V10.68 V (4.45%)712.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A5.66 V (2.36%)234.3 V9.34 V (3.89%)623.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A4.53 V (1.89%)235.5 V7.47 V (3.11%)498.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A3.78 V (1.57%)236.2 V6.23 V (2.6%)415.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A3.02 V (1.26%)237.0 V4.98 V (2.08%)332.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.27 V (0.94%)237.7 V3.74 V (1.56%)249.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 800 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 800 feet one-way at 240V (1-Phase), you need 350 kcmil copper wire. This produces a voltage drop of 6.47V (2.7%) and delivers 233.5V at the load.

What size aluminum wire is required for 110 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 6.23V (2.6%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.