🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

15 Amp Wire Size at 275 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 15 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 2.68%
Aluminum Wire (≤3% Drop)6 AWGDrop: 6.67V (2.78%)
Voltage at Load End233.6 VLoss: 6.43 V (96.4 W)
Power & Breaker (125%)3.6 kW20A Breaker Recommended

All AWG & kcmil Wire Gauges for 15 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A25.87 V (10.78%)214.1 V42.68 V (17.78%)388.1 WDrop/Amp High
12 AWG3.31 mm²20 A16.26 V (6.77%)223.7 V26.82 V (11.17%)243.9 WDrop/Amp High
10 AWG5.26 mm²30 A10.23 V (4.26%)229.8 V16.88 V (7.03%)153.5 W~ ≤5%
8 AWG8.37 mm²50 A6.43 V (2.68%)233.6 V10.61 V (4.42%)96.4 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A4.05 V (1.69%)236.0 V6.67 V (2.78%)60.7 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A2.54 V (1.06%)237.5 V4.2 V (1.75%)38.2 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A2.02 V (0.84%)238.0 V3.33 V (1.39%)30.3 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.6 V (0.67%)238.4 V2.64 V (1.1%)24.0 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.27 V (0.53%)238.7 V2.09 V (0.87%)19.0 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.01 V (0.42%)239.0 V1.66 V (0.69%)15.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.8 V (0.33%)239.2 V1.32 V (0.55%)12.0 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.63 V (0.26%)239.4 V1.04 V (0.44%)9.5 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.5 V (0.21%)239.5 V0.83 V (0.35%)7.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.42 V (0.18%)239.6 V0.7 V (0.29%)6.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.35 V (0.15%)239.6 V0.58 V (0.24%)5.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.3 V (0.13%)239.7 V0.5 V (0.21%)4.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.27 V (0.11%)239.7 V0.44 V (0.18%)4.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.21 V (0.09%)239.8 V0.35 V (0.15%)3.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.18 V (0.07%)239.8 V0.29 V (0.12%)2.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.14 V (0.06%)239.9 V0.23 V (0.1%)2.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.11 V (0.04%)239.9 V0.18 V (0.07%)1.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 15 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 15A load over 275 feet one-way at 240V (1-Phase), you need 8 AWG copper wire. This produces a voltage drop of 6.43V (2.68%) and delivers 233.6V at the load.

What size aluminum wire is required for 15 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 6.67V (2.78%).

What breaker size is needed for a 15A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (15A × 1.25 = 18.8A), which corresponds to a standard 20A circuit breaker.