⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

300 Amp Wire Size at 275 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 300 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)350 kcmil177.3 mm² · Drop: 2.53%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 7.01V (2.92%)
Voltage at Load End233.9 VLoss: 6.07 V (1821.1 W)
Power & Breaker (125%)72.0 kW400A Breaker Recommended

All AWG & kcmil Wire Gauges for 300 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A517.43 V (215.59%)0.0 V853.51 V (355.63%)155228.2 WDrop/Amp High
12 AWG3.31 mm²20 A325.15 V (135.48%)0.0 V536.35 V (223.48%)97545.2 WDrop/Amp High
10 AWG5.26 mm²30 A204.61 V (85.25%)35.4 V337.51 V (140.63%)61383.0 WDrop/Amp High
8 AWG8.37 mm²50 A128.58 V (53.58%)111.4 V212.1 V (88.38%)38575.2 WDrop/Amp High
6 AWG13.3 mm²65 A80.92 V (33.72%)159.1 V133.48 V (55.62%)24276.3 WDrop/Amp High
4 AWG21.15 mm²85 A50.89 V (21.2%)189.1 V83.94 V (34.97%)15265.9 WDrop/Amp High
3 AWG26.67 mm²100 A40.35 V (16.81%)199.6 V66.57 V (27.74%)12106.3 WDrop/Amp High
2 AWG33.62 mm²115 A32.01 V (13.34%)208.0 V52.81 V (22.0%)9603.6 WDrop/Amp High
1 AWG42.41 mm²130 A25.38 V (10.57%)214.6 V41.86 V (17.44%)7613.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A20.12 V (8.38%)219.9 V33.19 V (13.83%)6036.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A15.96 V (6.65%)224.0 V26.33 V (10.97%)4788.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A12.66 V (5.28%)227.3 V20.88 V (8.7%)3798.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.04 V (4.18%)230.0 V16.56 V (6.9%)3011.9 WDrop/Amp High
250 kcmil126.7 mm²255 A8.49 V (3.54%)231.5 V14.01 V (5.84%)2548.3 WDrop/Amp High
300 kcmil152.0 mm²285 A7.08 V (2.95%)232.9 V11.68 V (4.87%)2124.2 WDrop/Amp High
350 kcmil177.3 mm²310 A6.07 V (2.53%)233.9 V10.01 V (4.17%)1821.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A5.31 V (2.21%)234.7 V8.76 V (3.65%)1592.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A4.25 V (1.77%)235.8 V7.01 V (2.92%)1274.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A3.54 V (1.48%)236.5 V5.84 V (2.43%)1062.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.83 V (1.18%)237.2 V4.67 V (1.95%)849.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.12 V (0.89%)237.9 V3.5 V (1.46%)637.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 300 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 300A load over 275 feet one-way at 240V (1-Phase), you need 350 kcmil copper wire. This produces a voltage drop of 6.07V (2.53%) and delivers 233.9V at the load.

What size aluminum wire is required for 300 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 7.01V (2.92%).

What breaker size is needed for a 300A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (300A × 1.25 = 375.0A), which corresponds to a standard 400A circuit breaker.