⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

80 Amp Wire Size at 275 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 2.82%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 7.02V (2.93%)
Voltage at Load End233.2 VLoss: 6.77 V (541.4 W)
Power & Breaker (125%)19.2 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A137.98 V (57.49%)102.0 V227.6 V (94.83%)11038.4 WDrop/Amp High
12 AWG3.31 mm²20 A86.71 V (36.13%)153.3 V143.03 V (59.59%)6936.5 WDrop/Amp High
10 AWG5.26 mm²30 A54.56 V (22.73%)185.4 V90.0 V (37.5%)4365.0 WDrop/Amp High
8 AWG8.37 mm²50 A34.29 V (14.29%)205.7 V56.56 V (23.57%)2743.1 WDrop/Amp High
6 AWG13.3 mm²65 A21.58 V (8.99%)218.4 V35.6 V (14.83%)1726.3 WDrop/Amp High
4 AWG21.15 mm²85 A13.57 V (5.65%)226.4 V22.38 V (9.33%)1085.6 WDrop/Amp High
3 AWG26.67 mm²100 A10.76 V (4.48%)229.2 V17.75 V (7.4%)860.9 W~ ≤5%
2 AWG33.62 mm²115 A8.54 V (3.56%)231.5 V14.08 V (5.87%)682.9 W~ ≤5%
1 AWG42.41 mm²130 A6.77 V (2.82%)233.2 V11.16 V (4.65%)541.4 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A5.37 V (2.24%)234.6 V8.85 V (3.69%)429.2 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A4.26 V (1.77%)235.7 V7.02 V (2.93%)340.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A3.38 V (1.41%)236.6 V5.57 V (2.32%)270.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.68 V (1.12%)237.3 V4.42 V (1.84%)214.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.27 V (0.94%)237.7 V3.74 V (1.56%)181.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.89 V (0.79%)238.1 V3.11 V (1.3%)151.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.62 V (0.67%)238.4 V2.67 V (1.11%)129.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.42 V (0.59%)238.6 V2.34 V (0.97%)113.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.13 V (0.47%)238.9 V1.87 V (0.78%)90.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.94 V (0.39%)239.1 V1.56 V (0.65%)75.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.76 V (0.31%)239.2 V1.25 V (0.52%)60.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.57 V (0.24%)239.4 V0.93 V (0.39%)45.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 275 feet one-way at 240V (1-Phase), you need 1 AWG copper wire. This produces a voltage drop of 6.77V (2.82%) and delivers 233.2V at the load.

What size aluminum wire is required for 80 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 7.02V (2.93%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.