🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 275 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 2.77%
Aluminum Wire (≤3% Drop)4/0 AWGDrop: 6.9V (2.88%)
Voltage at Load End233.3 VLoss: 6.65 V (831.3 W)
Power & Breaker (125%)30.0 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A215.59 V (89.83%)24.4 V355.63 V (148.18%)26949.3 WDrop/Amp High
12 AWG3.31 mm²20 A135.48 V (56.45%)104.5 V223.48 V (93.12%)16934.9 WDrop/Amp High
10 AWG5.26 mm²30 A85.25 V (35.52%)154.7 V140.63 V (58.6%)10656.8 WDrop/Amp High
8 AWG8.37 mm²50 A53.58 V (22.32%)186.4 V88.38 V (36.82%)6697.1 WDrop/Amp High
6 AWG13.3 mm²65 A33.72 V (14.05%)206.3 V55.62 V (23.17%)4214.6 WDrop/Amp High
4 AWG21.15 mm²85 A21.2 V (8.83%)218.8 V34.97 V (14.57%)2650.3 WDrop/Amp High
3 AWG26.67 mm²100 A16.81 V (7.01%)223.2 V27.74 V (11.56%)2101.8 WDrop/Amp High
2 AWG33.62 mm²115 A13.34 V (5.56%)226.7 V22.0 V (9.17%)1667.3 WDrop/Amp High
1 AWG42.41 mm²130 A10.57 V (4.41%)229.4 V17.44 V (7.27%)1321.7 W~ ≤5%
1/0 AWG53.49 mm²150 A8.38 V (3.49%)231.6 V13.83 V (5.76%)1047.9 W~ ≤5%
2/0 AWG67.43 mm²175 A6.65 V (2.77%)233.3 V10.97 V (4.57%)831.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A5.28 V (2.2%)234.7 V8.7 V (3.63%)659.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A4.18 V (1.74%)235.8 V6.9 V (2.88%)522.9 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A3.54 V (1.47%)236.5 V5.84 V (2.43%)442.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.95 V (1.23%)237.0 V4.87 V (2.03%)368.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.53 V (1.05%)237.5 V4.17 V (1.74%)316.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.21 V (0.92%)237.8 V3.65 V (1.52%)276.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.77 V (0.74%)238.2 V2.92 V (1.22%)221.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.48 V (0.61%)238.5 V2.43 V (1.01%)184.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.18 V (0.49%)238.8 V1.95 V (0.81%)147.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.89 V (0.37%)239.1 V1.46 V (0.61%)110.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 275 feet one-way at 240V (1-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 6.65V (2.77%) and delivers 233.3V at the load.

What size aluminum wire is required for 125 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 4/0 AWG to maintain voltage drop at 6.9V (2.88%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.