🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

30 Amp Wire Size at 275 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 30 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 2.12%
Aluminum Wire (≤3% Drop)3 AWGDrop: 6.66V (2.77%)
Voltage at Load End234.9 VLoss: 5.09 V (152.7 W)
Power & Breaker (125%)7.2 kW40A Breaker Recommended

All AWG & kcmil Wire Gauges for 30 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A51.74 V (21.56%)188.3 V85.35 V (35.56%)1552.3 WDrop/Amp High
12 AWG3.31 mm²20 A32.52 V (13.55%)207.5 V53.63 V (22.35%)975.5 WDrop/Amp High
10 AWG5.26 mm²30 A20.46 V (8.53%)219.5 V33.75 V (14.06%)613.8 WDrop/Amp High
8 AWG8.37 mm²50 A12.86 V (5.36%)227.1 V21.21 V (8.84%)385.8 WDrop/Amp High
6 AWG13.3 mm²65 A8.09 V (3.37%)231.9 V13.35 V (5.56%)242.8 W~ ≤5%
4 AWG21.15 mm²85 A5.09 V (2.12%)234.9 V8.39 V (3.5%)152.7 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A4.04 V (1.68%)236.0 V6.66 V (2.77%)121.1 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A3.2 V (1.33%)236.8 V5.28 V (2.2%)96.0 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A2.54 V (1.06%)237.5 V4.19 V (1.74%)76.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.01 V (0.84%)238.0 V3.32 V (1.38%)60.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.6 V (0.67%)238.4 V2.63 V (1.1%)47.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.27 V (0.53%)238.7 V2.09 V (0.87%)38.0 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.0 V (0.42%)239.0 V1.66 V (0.69%)30.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.85 V (0.35%)239.2 V1.4 V (0.58%)25.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.71 V (0.3%)239.3 V1.17 V (0.49%)21.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.61 V (0.25%)239.4 V1.0 V (0.42%)18.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.53 V (0.22%)239.5 V0.88 V (0.36%)15.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.42 V (0.18%)239.6 V0.7 V (0.29%)12.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.35 V (0.15%)239.6 V0.58 V (0.24%)10.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.28 V (0.12%)239.7 V0.47 V (0.19%)8.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.21 V (0.09%)239.8 V0.35 V (0.15%)6.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 30 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 30A load over 275 feet one-way at 240V (1-Phase), you need 4 AWG copper wire. This produces a voltage drop of 5.09V (2.12%) and delivers 234.9V at the load.

What size aluminum wire is required for 30 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 3 AWG to maintain voltage drop at 6.66V (2.77%).

What breaker size is needed for a 30A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (30A × 1.25 = 37.5A), which corresponds to a standard 40A circuit breaker.