🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 1000 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.5%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 6.44V (3.09%)
Voltage at Load End202.8 VLoss: 5.2 V (1577.0 W)
Power & Breaker (125%)63.05 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 1000 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A950.53 V (456.98%)0.0 V1567.92 V (753.81%)288112.9 WDrop/Amp High
12 AWG3.31 mm²20 A597.31 V (287.17%)0.0 V985.28 V (473.69%)181049.8 WDrop/Amp High
10 AWG5.26 mm²30 A375.87 V (180.71%)0.0 V620.02 V (298.08%)113930.6 WDrop/Amp High
8 AWG8.37 mm²50 A236.21 V (113.56%)0.0 V389.64 V (187.33%)71598.0 WDrop/Amp High
6 AWG13.3 mm²65 A148.65 V (71.47%)59.3 V245.21 V (117.89%)45058.3 WDrop/Amp High
4 AWG21.15 mm²85 A93.48 V (44.94%)114.5 V154.2 V (74.13%)28334.5 WDrop/Amp High
3 AWG26.67 mm²100 A74.13 V (35.64%)133.9 V122.28 V (58.79%)22470.0 WDrop/Amp High
2 AWG33.62 mm²115 A58.81 V (28.27%)149.2 V97.0 V (46.64%)17825.0 WDrop/Amp High
1 AWG42.41 mm²130 A46.62 V (22.41%)161.4 V76.9 V (36.97%)14130.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A36.96 V (17.77%)171.0 V60.97 V (29.31%)11203.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A29.32 V (14.1%)178.7 V48.37 V (23.25%)8887.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A23.26 V (11.18%)184.7 V38.36 V (18.44%)7049.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A18.44 V (8.87%)189.6 V30.42 V (14.63%)5590.3 WDrop/Amp High
250 kcmil126.7 mm²255 A15.6 V (7.5%)192.4 V25.74 V (12.38%)4729.9 WDrop/Amp High
300 kcmil152.0 mm²285 A13.01 V (6.25%)195.0 V21.46 V (10.32%)3942.6 WDrop/Amp High
350 kcmil177.3 mm²310 A11.15 V (5.36%)196.8 V18.39 V (8.84%)3380.0 WDrop/Amp High
400 kcmil202.7 mm²335 A9.75 V (4.69%)198.2 V16.09 V (7.74%)2956.5 W~ ≤5%
500 kcmil253.4 mm²380 A7.8 V (3.75%)200.2 V12.87 V (6.19%)2364.9 W~ ≤5%
600 kcmil304.0 mm²420 A6.5 V (3.13%)201.5 V10.73 V (5.16%)1971.3 W~ ≤5%
750 kcmil380.0 mm²475 A5.2 V (2.5%)202.8 V8.58 V (4.13%)1577.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A3.9 V (1.88%)204.1 V6.44 V (3.09%)1182.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 1000 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 1000 feet one-way at 208V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 5.2V (2.5%) and delivers 202.8V at the load.

What size aluminum wire is required for 175 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 6.44V (3.09%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.