175 Amp Wire Size at 400 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 2.5%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 5.15V (2.48%)
Voltage at Load End202.8 VLoss: 5.2 V (1577.0 W)
Power & Breaker (125%)63.05 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 400 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A380.21 V (182.79%)0.0 V627.17 V (301.52%)115245.2 WDrop/Amp High
12 AWG3.31 mm²20 A238.92 V (114.87%)0.0 V394.11 V (189.48%)72419.9 WDrop/Amp High
10 AWG5.26 mm²30 A150.35 V (72.28%)57.7 V248.01 V (119.23%)45572.2 WDrop/Amp High
8 AWG8.37 mm²50 A94.48 V (45.43%)113.5 V155.86 V (74.93%)28639.2 WDrop/Amp High
6 AWG13.3 mm²65 A59.46 V (28.59%)148.5 V98.08 V (47.16%)18023.3 WDrop/Amp High
4 AWG21.15 mm²85 A37.39 V (17.98%)170.6 V61.68 V (29.65%)11333.8 WDrop/Amp High
3 AWG26.67 mm²100 A29.65 V (14.26%)178.3 V48.91 V (23.52%)8988.0 WDrop/Amp High
2 AWG33.62 mm²115 A23.52 V (11.31%)184.5 V38.8 V (18.65%)7130.0 WDrop/Amp High
1 AWG42.41 mm²130 A18.65 V (8.97%)189.4 V30.76 V (14.79%)5652.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A14.78 V (7.11%)193.2 V24.39 V (11.72%)4481.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A11.73 V (5.64%)196.3 V19.35 V (9.3%)3554.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.3 V (4.47%)198.7 V15.35 V (7.38%)2819.8 W~ ≤5%
4/0 AWG107.2 mm²230 A7.38 V (3.55%)200.6 V12.17 V (5.85%)2236.1 W~ ≤5%
250 kcmil126.7 mm²255 A6.24 V (3.0%)201.8 V10.3 V (4.95%)1891.9 W~ ≤5%
300 kcmil152.0 mm²285 A5.2 V (2.5%)202.8 V8.58 V (4.13%)1577.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A4.46 V (2.14%)203.5 V7.36 V (3.54%)1352.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A3.9 V (1.88%)204.1 V6.44 V (3.09%)1182.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A3.12 V (1.5%)204.9 V5.15 V (2.48%)946.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.6 V (1.25%)205.4 V4.29 V (2.06%)788.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.08 V (1.0%)205.9 V3.43 V (1.65%)630.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.56 V (0.75%)206.4 V2.57 V (1.24%)473.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 400 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 400 feet one-way at 208V (3-Phase), you need 300 kcmil copper wire. This produces a voltage drop of 5.2V (2.5%) and delivers 202.8V at the load.

What size aluminum wire is required for 175 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 5.15V (2.48%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.