🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 450 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 2.93%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 5.79V (2.41%)
Voltage at Load End233.0 VLoss: 7.02 V (2128.4 W)
Power & Breaker (125%)72.75 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 450 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A427.74 V (178.22%)0.0 V705.57 V (293.99%)129650.8 WDrop/Amp High
12 AWG3.31 mm²20 A268.79 V (112.0%)0.0 V443.38 V (184.74%)81472.4 WDrop/Amp High
10 AWG5.26 mm²30 A169.14 V (70.48%)70.9 V279.01 V (116.25%)51268.8 WDrop/Amp High
8 AWG8.37 mm²50 A106.3 V (44.29%)133.7 V175.34 V (73.06%)32219.1 WDrop/Amp High
6 AWG13.3 mm²65 A66.89 V (27.87%)173.1 V110.34 V (45.98%)20276.2 WDrop/Amp High
4 AWG21.15 mm²85 A42.07 V (17.53%)197.9 V69.39 V (28.91%)12750.5 WDrop/Amp High
3 AWG26.67 mm²100 A33.36 V (13.9%)206.6 V55.03 V (22.93%)10111.5 WDrop/Amp High
2 AWG33.62 mm²115 A26.46 V (11.03%)213.5 V43.65 V (18.19%)8021.2 WDrop/Amp High
1 AWG42.41 mm²130 A20.98 V (8.74%)219.0 V34.6 V (14.42%)6358.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A16.63 V (6.93%)223.4 V27.44 V (11.43%)5041.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A13.19 V (5.5%)226.8 V21.76 V (9.07%)3999.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A10.47 V (4.36%)229.5 V17.26 V (7.19%)3172.3 W~ ≤5%
4/0 AWG107.2 mm²230 A8.3 V (3.46%)231.7 V13.69 V (5.7%)2515.6 W~ ≤5%
250 kcmil126.7 mm²255 A7.02 V (2.93%)233.0 V11.58 V (4.83%)2128.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A5.85 V (2.44%)234.1 V9.66 V (4.02%)1774.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A5.02 V (2.09%)235.0 V8.28 V (3.45%)1521.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A4.39 V (1.83%)235.6 V7.24 V (3.02%)1330.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A3.51 V (1.46%)236.5 V5.79 V (2.41%)1064.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.93 V (1.22%)237.1 V4.83 V (2.01%)887.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.34 V (0.98%)237.7 V3.86 V (1.61%)709.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.76 V (0.73%)238.2 V2.9 V (1.21%)532.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 450 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 450 feet one-way at 240V (3-Phase), you need 250 kcmil copper wire. This produces a voltage drop of 7.02V (2.93%) and delivers 233.0V at the load.

What size aluminum wire is required for 175 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 5.79V (2.41%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.